CVE-2019-19276
mediumpriority · track · 21EPSS 0.010 · 63 %ileDEEUUSEPSS · scored 2026-10-27
A vulnerability has been identified in SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels (All versions < V16 Update 4). Specially crafted packets sent to port 161/udp can cause the SNMP service of affected devices to crash. A manual restart of the device is required to resume operation of the service.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)siemens_psirt
Update to V16 Update 4 or later version
https://support.industry.siemens.com/cs/ww/en/view/109775861/ - FixedSIMATIC HMI KTP Mobile Panelssiemens_psirt
Update to V16 Update 4 or later version
https://support.industry.siemens.com/cs/ww/en/view/109775861/ - FixedSIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)cisa_csaf_ot
Update to V16 Update 4 or later version
https://support.industry.siemens.com/cs/ww/en/view/109775861/ - FixedSIMATIC HMI KTP Mobile Panelscisa_csaf_ot
Update to V16 Update 4 or later version
https://support.industry.siemens.com/cs/ww/en/view/109775861/ - MitigationSIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)siemens_psirt
Disable SNMP if this is supported by the product. Disabling SNMP fully mitigates the vulnerability
- MitigationSIMATIC HMI KTP Mobile Panelssiemens_psirt
Disable SNMP if this is supported by the product. Disabling SNMP fully mitigates the vulnerability
- MitigationSIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP if this is supported by the product. Disabling SNMP fully mitigates the vulnerability
- MitigationSIMATIC HMI KTP Mobile Panelscisa_csaf_ot
Disable SNMP if this is supported by the product. Disabling SNMP fully mitigates the vulnerability
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (10)
Products and version ranges known to be affected.
- Siemens SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)All versions → V16 Update 4enisa_euvdEU
- siemens simatic hmi comfort panels firmware= 16nvdUScpe:2.3:o:siemens:simatic_hmi_comfort_panels_firmware:*:*:*:*:*:*:*:*
- siemens simatic hmi ktp mobile panels firmware= 16nvdUScpe:2.3:o:siemens:simatic_hmi_ktp_mobile_panels_firmware:*:*:*:*:*:*:*:*
advisories (2)
Vendor and ecosystem advisories describing this.
- SSA-594364SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime2021-05-11csaf · siemens_psirtDE
A denial-of-service vulnerability in WinCC Runtime could allow an unauthenticated attacker with network access to cause a denial-of-service condition in the SNMP service by sending crafted SNMP packets to port 161/udp. Siemens has released updates for the affected products and recommends to update to the latest versions.
- ICSA-21-131-06Siemens SNMP Implementation of WinCC Runtime2021-05-11icsa · cisa_csaf_otUS
A denial-of-service vulnerability in WinCC Runtime could allow an unauthenticated attacker with network access to cause a denial-of-service condition in the SNMP service by sending crafted SNMP packets to port 161/udp. Siemens has released updates for the affected products and recommends to update to the latest versions.
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (8)
External citations — patches, advisories, analysis.
- https://cert-portal.siemens.com/productcert/pdf/ssa-594364.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2019-19276cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-21-131-06cnnvd
- https://vigilance.fr/vulnerability/Siemens-SIMATIC-WinCC-denial-of-service-via-SNMP-35359cnnvd
- https://www.auscert.org.au/bulletins/ESB-2021.1602cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2021051309cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-594364.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-594364.pdfPatchVendor Advisorynvd