CVE-2019-13943

mediumpriority · track · 24EPSS 0.009 · 59 %ileEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
0.89% (59th) EPSS
CVSS 4.3 · medium
Is it mine?
20 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-27

A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The web interface could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify content of particular web pages, causing the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated to the web interface. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security. vulnerability was known.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedEN100 Ethernet module IEC 61850 variantcisa_csaf_ot

    Update to V4.37 https://support.industry.siemens.com/cs/us/en/view/109745821

  • MitigationEN100 Ethernet module DNP3 variantcisa_csaf_ot

    Block access to port 80/tcp and 443/tcp e.g. with an external firewall.

  • MitigationEN100 Ethernet module IEC 61850 variantcisa_csaf_ot

    Block access to port 80/tcp and 443/tcp e.g. with an external firewall.

  • MitigationEN100 Ethernet module IEC104 variantcisa_csaf_ot

    Block access to port 80/tcp and 443/tcp e.g. with an external firewall.

  • MitigationEN100 Ethernet module Modbus TCP variantcisa_csaf_ot

    Block access to port 80/tcp and 443/tcp e.g. with an external firewall.

  • MitigationEN100 Ethernet module PROFINET IO variantcisa_csaf_ot

    Block access to port 80/tcp and 443/tcp e.g. with an external firewall.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.2
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.3–7.2

v2.04.3mediumAV:N/AC:M/Au:N/C:N/I:P/A:Nprimary · NVD / NIST USexploitability 8.6 · impact 2.9
v3.16.1mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:Nprimary · NVD / NIST USexploitability 2.8 · impact 2.7
v3.17.2highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:L/A:L/E:P/RL:O/RC:Csecondary · CISA US
v3.15.6mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (20)

Products and version ranges known to be affected.

05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-19-344-07Siemens EN100 Ethernet Module (Update A)2019-12-10icsa · cisa_csaf_otUS

    Operators of critical power systems (e.g. TSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Secure Substations can be found at:

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2019-12-12modified 2026-06-17
09

references (9)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan