CVE-2019-13942
mediumpriority · track · 31EPSS 0.019 · 80 %ileEUUSEPSS · scored 2026-10-27
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedEN100 Ethernet module IEC 61850 variantcisa_csaf_ot
Update to V4.37 https://support.industry.siemens.com/cs/us/en/view/109745821
- MitigationEN100 Ethernet module DNP3 variantcisa_csaf_ot
Block access to port 80/tcp and 443/tcp e.g. with an external firewall.
- MitigationEN100 Ethernet module IEC 61850 variantcisa_csaf_ot
Block access to port 80/tcp and 443/tcp e.g. with an external firewall.
- MitigationEN100 Ethernet module IEC104 variantcisa_csaf_ot
Block access to port 80/tcp and 443/tcp e.g. with an external firewall.
- MitigationEN100 Ethernet module Modbus TCP variantcisa_csaf_ot
Block access to port 80/tcp and 443/tcp e.g. with an external firewall.
- MitigationEN100 Ethernet module PROFINET IO variantcisa_csaf_ot
Block access to port 80/tcp and 443/tcp e.g. with an external firewall.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5–7.5
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (20)
Products and version ranges known to be affected.
- siemens en100 ethernet module with firmware variant dnp3 tcpall versionsnvdUScpe:2.3:o:siemens:en100_ethernet_module_with_firmware_variant_dnp3_tcp:*:*:*:*:*:*:*:*
- siemens en100 ethernet module with firmware variant iec 61850< 4.37nvdUScpe:2.3:o:siemens:en100_ethernet_module_with_firmware_variant_iec_61850:*:*:*:*:*:*:*:*
- siemens en100 ethernet module with firmware variant iec104all versionsnvdUScpe:2.3:o:siemens:en100_ethernet_module_with_firmware_variant_iec104:*:*:*:*:*:*:*:*
- siemens en100 ethernet module with firmware variant modbus tcpall versionsnvdUScpe:2.3:o:siemens:en100_ethernet_module_with_firmware_variant_modbus_tcp:*:*:*:*:*:*:*:*
- siemens en100 ethernet module with firmware variant profinet ioall versionsnvdUScpe:2.3:o:siemens:en100_ethernet_module_with_firmware_variant_profinet_io:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-19-344-07Siemens EN100 Ethernet Module (Update A)2019-12-10icsa · cisa_csaf_otUS
Operators of critical power systems (e.g. TSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Secure Substations can be found at:
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (9)
External citations — patches, advisories, analysis.
- https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2019-13942cnnvd
- https://www.auscert.org.au/bulletins/ESB-2019.4620.2/cnnvd
- https://www.auscert.org.au/bulletins/ESB-2019.4620/cnnvd
- https://www.us-cert.gov/ics/advisories/icsa-19-344-07cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdfenisa_euvd
- https://www.us-cert.gov/ics/advisories/icsa-19-344-07enisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdfVendor Advisorynvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan