CVE-2018-13815
mediumpriority · track · 31EPSS 0.018 · 78 %ileEURUUSEPSS · scored 2026-10-27
A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSIMATIC S7-1200 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Update to V4.3 https://support.industry.siemens.com/cs/us/en/view/109763919
- FixedSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot
Update to V2.6 https://support.industry.siemens.com/cs/de/en/view/109478459
- MitigationSIMATIC S7-1200 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Apply cell-protection concept
- MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot
Apply cell-protection concept
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5–7.5
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (10)
Products and version ranges known to be affected.
- siemens simatic s7-1200 firmwareall versionsnvdUScpe:2.3:o:siemens:simatic_s7-1200_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-1500 firmware< 2.6nvdUScpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-18-317-05Siemens SIMATIC S7 (Update A)2018-11-13icsa · cisa_csaf_otUS
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (7)
External citations — patches, advisories, analysis.
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdfcnnvd
- https://ics-cert.us-cert.gov/advisories/ICSA-18-317-05cnnvd
- https://www.securityfocus.com/bid/105928cnnvd
- http://www.securityfocus.com/bid/105928enisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdfenisa_euvd
- http://www.securityfocus.com/bid/105928Third Party AdvisoryVDB Entrynvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdfVendor Advisorynvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan