CVE-2018-13805

mediumpriority · track · 31EPSS 0.016 · 75 %ileEURUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.58% (75th) EPSS
CVSS 5 · medium
Is it mine?
15 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

A vulnerability has been identified in SIMATIC ET 200SP Open Controller (All versions >= V2.0 and < V2.1.6), SIMATIC S7-1500 Software Controller (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 incl. F (All versions >= V2.0 and < V2.5). An attacker can cause a denial-of-service condition on the network stack by sending a large number of specially crafted packets to the PLC. The PLC will lose its ability to communicate over the network. This vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no privileges and no user interaction. An attacker could use this vulnerability to compromise availability of the network connectivity. At the time of advisory publication no public exploitation of this vulnerability was known.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedSIMATIC ET 200SP Open Controller (incl. SIPLUS variants)cisa_csaf_ot

    Update to V2.1.6 https://support.industry.siemens.com/cs/us/en/view/109759122

  • FixedSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot

    Update to V2.5 or newer https://support.industry.siemens.com/cs/us/en/ps/13717/dl

  • FixedSIMATIC S7-1500 Software Controllercisa_csaf_ot

    Update to V2.5 or newer https://support.industry.siemens.com/cs/us/en/view/109478528

  • MitigationSIMATIC ET 200SP Open Controller (incl. SIPLUS variants)cisa_csaf_ot

    Apply cell-protection concept

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot

    Apply cell-protection concept

  • MitigationSIMATIC S7-1500 Software Controllercisa_csaf_ot

    Apply cell-protection concept

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5–7.5

v2.05mediumAV:N/AC:L/Au:N/C:N/I:N/A:Pprimary · NVD / NIST USexploitability 10 · impact 2.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.06.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.15.3mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:P/RL:O/RC:Csecondary · CISA US
v3.15.3mediumAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · FSTEC (BDU) RU
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (15)

Products and version ranges known to be affected.

05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-18-282-05Siemens SIMATIC S7-1500, SIMATIC S7-1500 Software Controller and SIMATIC ET 200SP OpenController (Update A)2018-10-09icsa · cisa_csaf_otUS

    As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.

06

also known as (4)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

09

references (3)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan