CVE-2018-13798
highpriority · track · 31EPSS 0.020 · 80 %ileEUUSEPSS · scored 2026-10-22
A vulnerability has been identified in SICAM A8000 CP-8000 (All versions < V14), SICAM A8000 CP-802X (All versions < V14), SICAM A8000 CP-8050 (All versions < V2.00). Specially crafted network packets sent to port 80/TCP or 443/TCP could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the web server. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/TCP or 443/TCP. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the web server. A system reboot is required to recover the web service of the device. At the time of advisory update, exploit code for this security vulnerability is public.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSICAM A8000 CP-8000cisa_csaf_ot
Update to V14 - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8000
https://support.industry.siemens.com/cs/search - FixedSICAM A8000 CP-802Xcisa_csaf_ot
Update to V14 - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8000
https://support.industry.siemens.com/cs/search - FixedSICAM A8000 CP-8050cisa_csaf_ot
Update to V2.00 or higher - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8050
https://support.industry.siemens.com/cs/search - MitigationSICAM A8000 CP-8000cisa_csaf_ot
Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.
- MitigationSICAM A8000 CP-802Xcisa_csaf_ot
Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.
- MitigationSICAM A8000 CP-8050cisa_csaf_ot
Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5.3–7.8
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (12)
Products and version ranges known to be affected.
- Siemens AG SICAM A8000 CP-8000, SICAM A8000 CP-802X, SICAM A8000 CP-8050SICAM A8000 CP-8000 : All versions → V14enisa_euvdEU
- siemens sicam a8000 cp-8000 firmware< 14nvdUScpe:2.3:o:siemens:sicam_a8000_cp-8000_firmware:*:*:*:*:*:*:*:*
- siemens sicam a8000 cp-802x firmware< 14nvdUScpe:2.3:o:siemens:sicam_a8000_cp-802x_firmware:*:*:*:*:*:*:*:*
- siemens sicam a8000 cp-8050 firmware< 2.00nvdUScpe:2.3:o:siemens:sicam_a8000_cp-8050_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-19-038-01ICSA-19-038-01 Siemens SICAM A8000 RTU Series2019-01-08icsa · cisa_csaf_otUS
CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (4)
External citations — patches, advisories, analysis.
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan