CVE-2018-13798

highpriority · track · 31EPSS 0.020 · 80 %ileEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
1.99% (80th) EPSS
CVSS 7.8 · high
Is it mine?
12 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-22

A vulnerability has been identified in SICAM A8000 CP-8000 (All versions < V14), SICAM A8000 CP-802X (All versions < V14), SICAM A8000 CP-8050 (All versions < V2.00). Specially crafted network packets sent to port 80/TCP or 443/TCP could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the web server. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/TCP or 443/TCP. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the web server. A system reboot is required to recover the web service of the device. At the time of advisory update, exploit code for this security vulnerability is public.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedSICAM A8000 CP-8000cisa_csaf_ot

    Update to V14 - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8000

    https://support.industry.siemens.com/cs/search
  • FixedSICAM A8000 CP-802Xcisa_csaf_ot

    Update to V14 - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8000

    https://support.industry.siemens.com/cs/search
  • FixedSICAM A8000 CP-8050cisa_csaf_ot

    Update to V2.00 or higher - Download: https://support.industry.siemens.com/cs/search?search=a8000%20cp8050

    https://support.industry.siemens.com/cs/search
  • MitigationSICAM A8000 CP-8000cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.

  • MitigationSICAM A8000 CP-802Xcisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.

  • MitigationSICAM A8000 CP-8050cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:external firewall. Apply a Defence-in-Depth strategy.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5.3–7.8

v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USexploitability 10 · impact 6.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.05.3mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:H/RL:O/RC:Csecondary · CISA US
v3.06.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (12)

Products and version ranges known to be affected.

05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-19-038-01ICSA-19-038-01 Siemens SICAM A8000 RTU Series2019-01-08icsa · cisa_csaf_otUS

    CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2019-03-21modified 2026-06-17
09

references (4)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan