CVE-2017-6017

highpriority · track · 32EPSS 0.048 · 92 %ileEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
4.81% (92nd) EPSS
CVSS 7.8 · high
Is it mine?
26 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-27

A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationM1E CPUscisa_csaf_ot

    Set up a firewall blocking all remote/external access to Port 502

  • MitigationM340 CPUs with firmwarecisa_csaf_ot

    Set up a firewall blocking all remote/external access to Port 502

  • MitigationM580 CPUs with firmwarecisa_csaf_ot

    Set up a firewall blocking all remote/external access to Port 502

  • MitigationPremium CPUscisa_csaf_ot

    Set up a firewall blocking all remote/external access to Port 502

  • MitigationQuantum CPUs with firmwarecisa_csaf_ot

    Set up a firewall blocking all remote/external access to Port 502

02

cvss

Technical severity, 0–10. One row per scoring source.

7.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.8

v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USexploitability 10 · impact 6.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.06.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (26)

Products and version ranges known to be affected.

showing 20 of 26
05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-17-054-03Schneider Electric Modicon M340 PLC (Update A)2017-02-23icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability may render the device unresponsive requiring a physical reset of the PLC.

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2017-06-30modified 2026-06-17
09

references (9)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan