CVE-2016-8354

mediumpriority · track · 28EPSS 0.011 · 66 %ileEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.10% (66th) EPSS
CVSS 5.1 · medium
Is it mine?
4 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-24

An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationUnity Procisa_csaf_ot

    Schneider Electric recommends the following mitigation practices: Upgrade to Unity PRO Version 11.1. By default, it is not possible to launch this version of the simulator without any Unity PRO application associated. Exercise caution in selecting which project files are executed by the simulator. Do not trust files that come from unknown or untrusted sources. Use strong passwords to protect applications. It is not possible to load or to modify this application without being authenticated once the password protected application has been loaded onto the simulator.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5.1–7.5

v2.05.1mediumAV:N/AC:H/Au:N/C:P/I:P/A:Pprimary · NVD / NIST USexploitability 4.9 · impact 6.4
v3.07highCVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:Hprimary · NVD / NIST USexploitability 1 · impact 5.9
v3.07.5highCVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.06.4mediumCVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (4)

Products and version ranges known to be affected.

05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-16-306-03Schneider Electric Unity PRO Control Flow Management Vulnerability2016-08-05icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2017-02-13modified 2026-06-17