CVE-2016-4785

mediumpriority · track · 22OT risk · elevatedEPSS 0.027 · 86 %ileEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
2.68% (86th) EPSS
CVSS 5 · medium
Is it mine?
15 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-22

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedEN100 Ethernet modules as optional for Reyrollecisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-452237 at the following location:

  • FixedFirmware variant DNP3 TCP for EN100 Ethernet modulecisa_csaf_ot

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • FixedFirmware variant IEC 104 for EN100 Ethernet modulecisa_csaf_ot

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • FixedFirmware variant Modbus TCP for EN100 Ethernet modulecisa_csaf_ot

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • FixedFirmware variant PROFINET IO for EN100 Ethernet modulecisa_csaf_ot

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • FixedIEC 61850 firmwarecisa_csaf_ot

    In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:

  • FixedTPOP firmwarecisa_csaf_ot

    In addition, ICS-CERT recommends that users take the following measures to protect themselves from social engineering attacks:

  • MitigationEN100 Ethernet module included in SIPROTEC 4cisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationEN100 Ethernet module included in SIPROTEC Compactcisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationSIPROTEC Compact model 7SJ80 with Ethernet Service Interface on Port A Firmwarecisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationSIPROTEC Compact models 7RW80 with Ethernet Service Interface on Port Acisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationSIPROTEC Compact models 7SJ81 with Ethernet Service Interface on Port Acisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationSIPROTEC Compact models 7SK81 with Ethernet Service Interface on Port Acisa_csaf_ot

    For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-547990 at the following location: (http://www.siemens.com/cert/advisories)

    http://www.siemens.com/cert/advisories
  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80cisa_csaf_ot

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SD686cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ686cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7UT686cisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

02

cvss

Technical severity, 0–10. One row per scoring source.

5.3
010

base score 0–10 · higher = more severe · hover a vector to decode

v2.05mediumAV:N/AC:L/Au:N/C:P/I:N/A:Nprimary · NVD / NIST USexploitability 10 · impact 2.9
v3.05.3mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:Nprimary · NVD / NIST USexploitability 3.9 · impact 1.4
v3.05.3mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:Nsecondary · CISA US
v3.04.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (15)

Products and version ranges known to be affected.

05

advisories (4)

Vendor and ecosystem advisories describing this.

  • ICSA-16-140-02Siemens SIPROTEC Information Disclosure Vulnerabilities (Update B)2016-02-20icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

  • ICSA-17-187-02Siemens Reyrolle2017-07-06icsa · cisa_csaf_otUS

    ATTENTION: Remotely exploitable/low skill level to exploit.

  • ICSA-17-187-03FICSA-17-187-03F Siemens SIPROTEC 4 and SIPROTEC Compact (Update F)2017-07-04icsa · cisa_csaf_otUS

    CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

  • ICSA-17-334-01Siemens SWT30002017-11-30icsa · cisa_csaf_otUS

    ATTENTION: Remotely exploitable/low skill level to exploit.

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2016-05-31modified 2026-06-17
09

references (15)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan