CVE-2013-2807
highpriority · track · 31EPSS 0.039 · 90 %ileEUUSEPSS · scored 2026-10-27
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
No vendor fix yet; a mitigation is available.
- MitigationFactoryTalk Services Platform and RSLinx Enterprisecisa_csaf_ot
Rockwell Automation’s recommendation to asset owners using FTSP or RSLinx CPR9 through CPR9-SR4 is to upgrade to CPR9-SR5 or newer. Rockwell Automation also recommends that all asset owners using FTSP or RSLinx CPR9-SR5 and newer should apply the correlating patch for the version they are using.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.8
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (26)
Products and version ranges known to be affected.
- rockwellautomation rslinx enterprise= 5.10.00nvdUScpe:2.3:a:rockwellautomation:rslinx_enterprise:*:*:*:*:*:*:*:*
- rockwellautomation rslinx enterprise= 5.10.01nvdUScpe:2.3:a:rockwellautomation:rslinx_enterprise:*:*:*:*:*:*:*:*
- rockwellautomation rslinx enterprise= 5.20.00nvdUScpe:2.3:a:rockwellautomation:rslinx_enterprise:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-13-095-02ARockwell Automation FactoryTalk and RSLinx Vulnerabilities2013-01-07icsa · cisa_csaf_otUS
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (5)
External citations — patches, advisories, analysis.
- http://www.rockwellautomation.com/rockwellsoftware/design/rslinx/overview.pagePatchcnnvd
- https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02cnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2013-2807cnnvd
- https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02enisa_euvd
- https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02Third Party AdvisoryUS Government Resourcenvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan