CVE-2013-0663

mediumpriority · track · 39EPSS 0.060 · 93 %ileexploit · PoCEURUUS
grimoire priorityP1 · Urgent
Exploitable?
Public exploit
1 exploit · PoC
Likely / severe?
5.96% (93rd) EPSS
CVSS 6.8 · medium
Is it mine?
19 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-28

Cross-site request forgery (CSRF) vulnerability on the Schneider Electric Quantum 140NOE77111, 140NOE77101, and 140NWM10000; M340 BMXNOC0401, BMXNOE0100x, and BMXNOE011xx; and Premium TSXETY4103, TSXETY5103, and TSXWMY100 PLC modules allows remote attackers to hijack the authentication of arbitrary users for requests that execute commands, as demonstrated by modifying HTTP credentials.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationModicon M340 PLC modulescisa_csaf_ot

    Schneider Electric has issued a patch for the HTTP and FTP service that is available on selected Quantum PLC. This patch contains a new feature that allows the user to disable HTTP service on certain modules. The patch can be found on the Schneider Electric website

  • MitigationPremium PLC modulescisa_csaf_ot

    Schneider Electric has issued a patch for the HTTP and FTP service that is available on selected Quantum PLC. This patch contains a new feature that allows the user to disable HTTP service on certain modules. The patch can be found on the Schneider Electric website

  • MitigationQuantum PLC modulescisa_csaf_ot

    Schneider Electric has issued a patch for the HTTP and FTP service that is available on selected Quantum PLC. This patch contains a new feature that allows the user to disable HTTP service on certain modules. The patch can be found on the Schneider Electric website

02

cvss

Technical severity, 0–10. One row per scoring source.

8.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.1–8.5

v2.06.8mediumAV:N/AC:M/Au:N/C:P/I:P/A:Pprimary · NVD / NIST USexploitability 8.6 · impact 6.4
v2.08.5highAV:N/AC:M/Au:S/C:C/I:C/A:Csecondary · CISA US
v2.06.8mediumAV:N/AC:M/Au:N/C:P/I:P/A:Psecondary · FSTEC (BDU) RU
v2.06.1mediumAV:N/AC:M/Au:N/C:P/I:P/A:P/E:POCsecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

exploits (1)

Public proof-of-concept and weaponised exploit code.

05

affected products (19)

Products and version ranges known to be affected.

06

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-13-077-01BSchneider Electric PLCs Vulnerabilities2013-12-20icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

07

also known as (5)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

10

references (12)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan