CVE-2011-4508

highpriority · track · 38EPSS 0.030 · 87 %ileEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.98% (87th) EPSS
CVSS 9.3 · high
Is it mine?
27 products
Check your exposure
Who says so?
3 sources
enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-22

The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication tokens for cookies, which makes it easier for remote attackers to bypass authentication via a crafted cookie.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationMultiple SIMATIC Panelscisa_csaf_ot

    Product documentation has been updated to tell the user how to set a proper password during initial setup to remove the risk of the default password vulnerability.

  • MitigationSIMATIC WinCC Runtime Advancedcisa_csaf_ot

    Product documentation has been updated to tell the user how to set a proper password during initial setup to remove the risk of the default password vulnerability.

  • MitigationSIMATIC WinCC flexible RTcisa_csaf_ot

    Product documentation has been updated to tell the user how to set a proper password during initial setup to remove the risk of the default password vulnerability.

  • MitigationMultiple SIMATIC HMI panels (TP, OP, MP, Comfort Panels, Mobile Panels)cisa_csaf_ot

    Lack of telnet daemon authentication - Because telnet is a clear text protocol, customers are advised to be aware of corresponding risks. The telnet daemon is disabled by default in product versions WinCC flexible 2008 SP3 and newer, as well as WinCC V11 (TIA Portal) SP2 and newer. Siemens recommends disabling the telnet function on SIMATIC panels when telnet is not actively being used.

  • MitigationWinCC V11 (TIA portal)cisa_csaf_ot

    Lack of telnet daemon authentication - Because telnet is a clear text protocol, customers are advised to be aware of corresponding risks. The telnet daemon is disabled by default in product versions WinCC flexible 2008 SP3 and newer, as well as WinCC V11 (TIA Portal) SP2 and newer. Siemens recommends disabling the telnet function on SIMATIC panels when telnet is not actively being used.

  • MitigationWinCC V11 Runtime Advancedcisa_csaf_ot

    Lack of telnet daemon authentication - Because telnet is a clear text protocol, customers are advised to be aware of corresponding risks. The telnet daemon is disabled by default in product versions WinCC flexible 2008 SP3 and newer, as well as WinCC V11 (TIA Portal) SP2 and newer. Siemens recommends disabling the telnet function on SIMATIC panels when telnet is not actively being used.

  • MitigationWinCC flexiblecisa_csaf_ot

    Lack of telnet daemon authentication - Because telnet is a clear text protocol, customers are advised to be aware of corresponding risks. The telnet daemon is disabled by default in product versions WinCC flexible 2008 SP3 and newer, as well as WinCC V11 (TIA Portal) SP2 and newer. Siemens recommends disabling the telnet function on SIMATIC panels when telnet is not actively being used.

  • MitigationWinCC flexible Runtimecisa_csaf_ot

    Lack of telnet daemon authentication - Because telnet is a clear text protocol, customers are advised to be aware of corresponding risks. The telnet daemon is disabled by default in product versions WinCC flexible 2008 SP3 and newer, as well as WinCC V11 (TIA Portal) SP2 and newer. Siemens recommends disabling the telnet function on SIMATIC panels when telnet is not actively being used.

02

cvss

Technical severity, 0–10. One row per scoring source.

9.3
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · high–critical · 7.9–9.3

v2.09.3highAV:N/AC:M/Au:N/C:C/I:C/A:Cprimary · NVD / NIST USexploitability 8.6 · impact 10
v2.09.3criticalAV:N/AC:M/Au:N/C:C/I:C/A:Csecondary · CISA US
v2.07.9highAV:N/AC:M/Au:N/C:C/I:C/A:C/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (27)

Products and version ranges known to be affected.

showing 20 of 27
05

advisories (2)

Vendor and ecosystem advisories describing this.

  • ICSA-11-356-01Siemens Simatic HMI Authentication Vulnerabilities2011-09-24icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

  • ICSA-12-030-01ASiemens SIMATIC WinCC Vulnerabilities2012-11-02icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

06

also known as (2)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

published 2012-02-03modified 2026-06-16
09

references (4)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan