CVE-2026-59693
mediumPriorität · verfolgen · 0EPSS 0.002 · 15. PerzentilDEEUNLUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- BehobenDesigo DXR2siemens_psirt
Update to V01.21.233.16-7862 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC3siemens_psirt
Update to V01.21.233.16-7862 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC4siemens_psirt
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC5.E003siemens_psirt
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC5.E24siemens_psirt
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC7siemens_psirt
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo DXR2cisa_csaf_ot
Update to V01.21.233.16-7862 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC3cisa_csaf_ot
Update to V01.21.233.16-7862 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC4cisa_csaf_ot
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC5.E003cisa_csaf_ot
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC5.E24cisa_csaf_ot
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
- BehobenDesigo PXC7cisa_csaf_ot
Update to V02.21.194.36-2715 or later version Please contact your local Siemens office for additional support in obtaining the update.
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · low–medium · 1.3–5.3
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (49)
Betroffene Produkte und Versionsbereiche.
Advisories (3)
Hersteller- und Ökosystem-Meldungen dazu.
- NCSC-2026-0282Kwetsbaarheden verholpen in Siemens productenNL2026-08-11csaf · ncsc_nlNL
Siemens heeft kwetsbaarheden verholpen in diverse producten als Desigo, Parasolid, RUGGEDCOM, SIMATIC, Siveillance en Solid Edge.
- SSA-781903SSA-781903: Denial of Service Vulnerability in Desigo DXR and PXC Controllers2026-08-11csaf · siemens_psirtDE
A vulnerability in Desigo DXR and PXC controllers has been identified that could allow an attacker to cause denial of service conditions by sending malformed BACnet packets. Recovery requires a device reset or reboot to restore normal functionality. Siemens has released new versions for the affected products and recommends to update to the latest versions.
- ICSA-26-225-08Siemens Desigo DXR and PXC Controllers2026-08-11icsa · cisa_csaf_otUS
A vulnerability in Desigo DXR and PXC controllers has been identified that could allow an attacker to cause denial of service conditions by sending malformed BACnet packets. Recovery requires a device reset or reboot to restore normal functionality. Siemens has released new versions for the affected products and recommends to update to the latest versions.