CVE-2025-41659

highPriorität · verfolgen · 0EPSS 0.002 · 12. PerzentilCHDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.22% (12th) EPSS
CVSS 8.3 · high
Is it mine?
87 products
Prüfe deine Angriffsfläche
Who says so?
10 sources
cnnvd · enisa_euvd · fstec_bdu · abb_psirt

EPSS · bewertet 2026-10-22

A low-privileged attacker can remotely access the PKI folder of the CODESYS Control runtime system and thus read and write certificates and its keys. This allows sensitive data to be extracted or to accept certificates as trusted. Although all services remain available, only unencrypted communication is possible if the certificates are deleted.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenAC500 V3abb_psirt

    The problem is corrected in the following product versions: - AC500 V3 firmware version 3.9.0 ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.9.0. Automation Builder 2.9.0 is available for download from the related download site. https://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download

  • Behobencodesys_psirt

    Update the following products to version 3.5.21.20. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/. Following our general recommendation that the PKI should only be managed via the dedicated X.509 API or the corresponding online services of the CODESYS Control runtime system, the programmatic direct access via SysFile or SysDir operations or online access via the CODESYS file transfer services is denied after an update to a fixed product version. For compatibility reasons, the old behavior can be restored for applications that use these accesses via the following setting: [CmpOpenSSL] EnforceBlacklistOnPKIDir=0 However, we strongly recommend keeping the new default.

  • BehobenFirmware 3.1 installed on CR3171ifm_psirt

    will be fixed in Firmware Version 3.3

    https://www.ifm.com/de/en/product/CR3171#documents
  • BehobenFirmware 3.2 installed on CR3171ifm_psirt

    will be fixed in Firmware Version 3.3

    https://www.ifm.com/de/en/product/CR3171#documents
  • BehobenCOMBIVIS Control Runtimekeb_psirt

    Update the COMBIVIS Control Runtime service to version 2.1.0.

  • BehobenAC500 V3cisa_csaf_ot

    The problem is corrected in the following product versions: - AC500 V3 firmware version 3.9.0 ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.9.0. Automation Builder 2.9.0 is available for download from the related download site. https://www.abb.com/global/en/areas/motion/digital-tools/automation-builder/software-download

  • MitigationAC500 V3abb_psirt

    Refer to section “General security recommendations” for further advise on how to keep your system secure.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFirmware 3.1 installed on CR3171ifm_psirt

    deactivate CodeSys enviroment on device

  • MitigationFirmware 3.2 installed on CR3171ifm_psirt

    deactivate CodeSys enviroment on device

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationAC500 V3cisa_csaf_ot

    Refer to section “General security recommendations” for further advise on how to keep your system secure.

  • WorkaroundAC500 V3abb_psirt

    No workarounds are available

  • WorkaroundAC500 V3cisa_csaf_ot

    No workarounds are available

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.3
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen

v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L/E:F/RL:O/RC:Csecondary · CISA US
v3.18.3highAV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · FSTEC (BDU) RU
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · ENISA EU
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · info@cert.vde.comAusnutzbarkeit 2.8 · Auswirkung 5.5
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · Festo PSIRT DE
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · ifm PSIRT DE
v3.17.6highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L/E:Usecondary · CVSS-BT (t0sche)
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:L/E:F/RL:O/RC:Csecondary · ABB PSIRT
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · CODESYS PSIRT
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Lsecondary · KEB PSIRT
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (87)

Betroffene Produkte und Versionsbereiche.

06

Advisories (8)

Hersteller- und Ökosystem-Meldungen dazu.

  • 3ADR011524AC500 V3 Multiple vulnerabilities2026-02-24csaf · abb_psirtCH

    ABB became aware of severe vulnerability in the products versions listed as affected in the advisory. An update is available that resolves these vulnerabilities. An attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691).

  • Advisory2025-07_VDE-2025-051CODESYS Control V3 - Exposed PKI folder2025-08-04csaf · codesys_psirtDE

    A vulnerability in the CODESYS Control runtime system allows low-privileged remote attackers to access the PKI folder via CODESYS protocol, enabling them to read and write certificates and keys. This exposes sensitive cryptographic data and allows unauthorized certificates to be trusted. However, all services remain available, only certificate based encryption and signing features are concerned. The issue affects systems using the optional CmpOpenSSL component for cryptographic operations. **Update 1.1.0, 01.09.2025:** Updated remediation category - fixed SL runtimes are now available.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2026-005ifm: Multiple Vulnerabilities in CR31712026-05-06csaf · ifm_psirtDE

    The Firmware installed on the CR3171 is impacted by various CODESYS vulnerabilities.

  • VDE-2026-105KEB Automation: Multiple Vulnerabilities in COMBIVIS Control Runtime2026-10-08csaf · keb_psirtDE

    The Docker-based COMBIVIS Control Runtime service is affected by several vulnerabilities in CODESYS Runtime Toolkit 3.5.21.10. These vulnerabilities are resolved in COMBIVIS Control Runtime 2.1.0.

  • WID-SEC-W-2025-1705CODESYS: Mehrere SchwachstellenDeutsch2025-08-03csaf · cert_bundDE

    Ein Angreifer kann mehrere Schwachstellen in CODESYS ausnutzen, um einen Denial-of-Service-Zustand auszulösen, Daten zu manipulieren und vertrauliche Informationen preiszugeben.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • ICSA-26-132-03ABB AC500 V3 Multiple Vulnerabilities2026-02-24icsa · cisa_csaf_otUS

    ABB became aware of severe vulnerability in the products versions listed as affected in the advisory. An update is available that resolves these vulnerabilities. An attacker who successfully exploited these vulnerabilities could bypass the user management and read visualization files (CVE-2025-2595), read and write certificates and keys (CVE-2025-41659) or cause a denial-of-service (DoS) (CVE-2025-41691).