CVE-2025-2813

highPriorität · verfolgen · 0EPSS 0.007 · 51. PerzentilDEEU
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.66% (51st) EPSS
CVSS 7.5 · high
Is it mine?
36 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · bosch_psirt · phoenix_contact_psirt

EPSS · bewertet 2026-10-27

An unauthenticated remote attacker can cause a Denial of Service by sending a large number of requests to the http service on port 80.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • Behobenphoenix_contact_psirt

    Affected bus couplers are designed and developed for the use in closed industrial networks. Phoenix Contact therefore strongly recommends using the devices exclusively in closed networks and protected by a suitable firewall. To further improve security, fixed firmware versions are available for the items listed in the "Fixed" section. A fix for products marked as "discontinued" is not planned. All other listed products will receive a bugfix at the next revision.

  • MitigationBosch Rexroth AG R-IL ETH BK DI8 DO4 2TX-PAC (R911171726)bosch_psirt

    If possible, protect your network by blocking access to port 80 on the affected devices.

  • MitigationBosch Rexroth AG S20-EIP-BK (R911173904)bosch_psirt

    If possible, protect your network by blocking access to port 80 on the affected devices.

  • MitigationBosch Rexroth AG S20-ETH-BK (R911173905)bosch_psirt

    If possible, protect your network by blocking access to port 80 on the affected devices.

  • MitigationBosch Rexroth AG S20-PN-BK+ (R911173359)bosch_psirt

    If possible, protect your network by blocking access to port 80 on the affected devices.

  • Mitigationphoenix_contact_psirt

    This product was designed for use in closed industrial networks. Phoenix Contact strongly recommends operating network-capable devices in closed networks or protected with a suitable firewall. For detailed information on our recommendations for measures to protect network-capable devices, please refer to our [application note](https://dam-mdc.phoenixcontact.com/asset/156443151564/0a870ae433c19148b80bd760f3a1c1f2/107913_en_03.pdf). If the use of scanners is mandatory for network security in closed production networks, it is recommended to exclude or disable denial of service tests that target port 80. Most network scanners offer options to individually disable certain tests or to apply exclusions by clustering device types and test categorization functions.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.9–7.5

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · info@cert.vde.comAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Phoenix Contact PSIRT DE
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Bosch PSIRT DE
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (36)

Betroffene Produkte und Versionsbereiche.

06

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • BOSCH-SA-757244BOSCH-SA-7572442025-08-14csaf · bosch_psirtDE

    Several fieldbus couplers sold by Bosch Rexroth contain technology from Phoenix Contact. The manufacturer published a security bulletin about a weakness in the web-based administration interface. A successful attack leads to an overload of the device and the hardware watchdog is triggered. Process data behaves according to the configured substitute value behavior. The bus coupler requires a manual restart (resetting the power supply, pressing the reset button or executing the SNMP reset command) to reestablish communication within the Industrial Ethernet (e.g. PROFINET IO, Modbus/TCP, EtherNet/IP).

  • VDE-2025-029Phoenix Contact: Security Advisory for AXL F BK and IL BK bus couplers2025-05-13csaf · phoenix_contact_psirtDE

    A denial of service (DoS) attack targeting port 80 (http service) can overload the device (CWE-770). This behaviour has been observed when running network security scanners.

07

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry