CVE-2025-11043

highPriorität · verfolgen · 0EPSS 0.002 · 14. PerzentilCHEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.24% (14th) EPSS
CVSS 7.4 · high
Is it mine?
8 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · abb_psirt · cisa_csaf_ot

EPSS · bewertet 2026-10-27

An Improper Certificate Validation vulnerability in the OPC-UA client and ANSL over TLS client used in Automation Studio versions before 6.5 could allow an unauthenticated attacker on the network to position themselves to intercept and interfere with data exchanges.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenAutomation Studioabb_psirt

    The problem is corrected in the following product versions: B&R Automation Studio version 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is de-scribed in the user manual.

  • BehobenAutomation Studiocisa_csaf_ot

    The problem is corrected in the following product versions: B&R Automation Studio version 6.5 B&R recommends that customers apply the update at earliest convenience. The process to install updates is described in the user manual. The step to identify the installed product version is de-scribed in the user manual.

  • MitigationAutomation Studioabb_psirt

    To exploit this vulnerability, an attacker would need to intercept and redirect the communication between B&R Automation Studio and the target server, as well as present manipulated certificates that pass validation checks. B&R recommends operating B&R Automation Studio within Level 2 of the ABB ICS Cyber Security Reference Architecture when connecting to Level 1 devices via ANSL over TLS or OPC-UA. Operating in this trusted environment reduces the risk of successful exploitation drastically. Refer to section “General security recommendations” for further advise on how to keep your system secure.

  • MitigationAutomation Studiocisa_csaf_ot

    To exploit this vulnerability, an attacker would need to intercept and redirect the communication between B&R Automation Studio and the target server, as well as present manipulated certificates that pass validation checks. B&R recommends operating B&R Automation Studio within Level 2 of the ABB ICS Cyber Security Reference Architecture when connecting to Level 1 devices via ANSL over TLS or OPC-UA. Operating in this trusted environment reduces the risk of successful exploitation drastically. Refer to section “General security recommendations” for further advise on how to keep your system secure.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.1
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–critical · 6.9–9.1

v3.17.4highCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N/RL:O/RC:Csecondary · CISA US
v3.17.4highCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:Nsecondary · cybersecurity@ch.abb.comAusnutzbarkeit 2.2 · Auswirkung 5.2
v3.17.4highCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N/RL:O/RC:Csecondary · ABB PSIRT
v4.09.1criticalCVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.09.1criticalCVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@ch.abb.com
v4.06.9mediumCVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Trackcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (8)

Betroffene Produkte und Versionsbereiche.

06

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • SA25P004Automation Studio Insufficient Server Certificate Validation2026-01-19csaf · abb_psirtCH

    ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that resolves a vulnerability. Successful exploitation of this vulnerability may enable an attacker to masquerade as a trusted party when B&R Automation Studio establishes a connection with a server via the ANSL over TLS or OPC-UA protocol.

  • ICSA-26-125-04ABB B&R Automation Studio2026-01-19icsa · cisa_csaf_otUS

    ABB became aware of vulnerability in the product versions listed as affected in the advisory. An update is available that resolves a vulnerability. Successful exploitation of this vulnerability may enable an attacker to masquerade as a trusted party when B&R Automation Studio establishes a connection with a server via the ANSL over TLS or OPC-UA protocol.

07

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2026-01-19geändert 2026-06-17
09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan