CVE-2025-0694

mediumPriorität · verfolgen · 0EPSS 0.003 · 19. PerzentilDEEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
0.28% (19th) EPSS
CVSS 6.6 · medium
Is it mine?
101 products
Prüfe deine Angriffsfläche
Who says so?
7 sources
cnnvd · enisa_euvd · cert_bund · cisa_csaf_ot

EPSS · bewertet 2026-10-22

Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • Behobencodesys_psirt

    Update the following products to version 3.5.21.0. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS Runtime Toolkit If removable media is configured for the CODESYS Control runtime, make sure that any additional removable storage beyond the boot partition is set as volatile in the CODESYS Control configuration file with the entry "PlaceholderFilePath.<n>.Volatile=1". Then the fixed CODESYS Control runtime systems ensure that only configured/permitted paths can be accessed, even with a symbolic link on a removable media. Example: [SysFile] PlaceholderFilePath.1=/media/usb, $USB$ PlaceholderFilePath.1.View=1 PlaceholderFilePath.1.Volatile=1 The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download.

  • Behobenwago_psirt

    Update to Firmware version 04.08.01 (FW30), 01.05.01 (FW05), 03.10.11 (FW22 Patch 2). For the latest Custom Firmware please contact the WAGO support.

  • Mitigationcodesys_psirt

    Regardless of the vulnerability described here, CODESYS GmbH recommends that physical access to the controller should only be granted to authorized persons. Especially in the case of productive control systems, physical manipulation of the controller can affect the controlled machine or process. This generally recommended restriction of access also reduces the attack surface for this vulnerability, as its exploitation requires physical access. To exploit this vulnerability, a successful login to the affected product is required. The online user management therefore protects from exploiting this security vulnerability. CODESYS GmbH strongly recommends using the online user management, which is enforced by default. This not only prevents from accessing the file system with malicious symbolic links, but also suppresses modifying the PLC application, or starting, stopping, debugging or other actions on a known working PLC application that could potentially disrupt a machine or system. To fully mitigate this vulnerability, system administrators can restrict the use of removable media to devices that do not support symbolic links, such as FAT16 or FAT32. Since these file systems lack symbolic link functionality, this effectively prevents any symbolic link-based attacks. Alternatively, remove PlaceHolderFilePath settings from the CODESYS Control configuration file, which point to removable media such as: [SysFile] PlaceholderFilePath.1=/media/usb, $USB$

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

6.6
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen

v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · ENISA EU
v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · info@cert.vde.comAusnutzbarkeit 0.7 · Auswirkung 5.9
v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · WAGO PSIRT DE
v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · Festo PSIRT DE
v3.16.1mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.16.6mediumCVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · CODESYS PSIRT
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (101)

Betroffene Produkte und Versionsbereiche.

20 von 101 angezeigt
06

Advisories (5)

Hersteller- und Ökosystem-Meldungen dazu.

  • Advisory2025-03_VDE-2025-015CODESYS Control V3 removable media path traversal2025-03-18csaf · codesys_psirtDE

    A low privileged attacker with physical access to a controller, that supports removable media and is running a CODESYS Control runtime system, can exploit the insufficient path validation by connecting removable media with a file system supporting symbolic links. This could allow the attacker to bypass SysFile restrictions and gain unauthorized access to the entire file system.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2025-062WAGO: Multiple Vulnerabilities in CODESYS components2025-11-03csaf · wago_psirtDE

    Several WAGO firmwares installed on different devices are impacted by various CODESYS vulnerabilities. These affect the runtime, visualization, and OPC UA server.

  • WID-SEC-W-2025-0582CODESYS Control: Schwachstelle ermöglicht Umgehen von SicherheitsvorkehrungenDeutsch2025-03-17csaf · cert_bundDE

    Ein lokaler Angreifer kann eine Schwachstelle in CODESYS Control ausnutzen, um Sicherheitsvorkehrungen zu umgehen.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

07

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (5)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan