CVE-2024-8937
highPriorität · verfolgen · 0EPSS 0.006 · 48. PerzentilEURUUSEPSS · bewertet 2026-10-27
CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a potential arbitrary code execution after a successful Man-In-The Middle attack followed by sending a crafted Modbus function call to tamper with memory area involved in the authentication process.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- BehobenModicon M340 CPU Firmware Versions prior to SV3.65 installed on Modicon M340 CPU Controller (part numbers BMXP34*)cisa_csaf_ot
Version SV3.65 of Modicon M340 firmware includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/1468- modicon-m340
https://www.se.com/ww/en/product-range/1468-modicon-m340 - BehobenModicon MC80 Firmware Versions prior to SV2.1 installed on Modicon MC80 Controller (part numbers BMKC80)cisa_csaf_ot
Version SV2.1 of Modicon MC80 firmware includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/62396-modicon-mc80
https://www.se.com/ww/en/product-range/62396-modicon-mc80 - BehobenModicon Momentum Unity M1E Processor Firmware Versions prior to SV2.80 installed on Modicon Momentum Unity M1E Processor Controller (171CBU*)cisa_csaf_ot
Version SV2.80 of Modicon Momentum firmware includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/535-modicon-momentum
https://www.se.com/ww/en/product-range/535-modicon-momentum - MitigationModicon M340 CPU Firmware Versions prior to SV3.65 installed on Modicon M340 CPU Controller (part numbers BMXP34*)cisa_csaf_ot
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M340 for Ethernet Communications Modules and Processors User Manual” chapter “Messaging Configuration Parameters”: https://www.se.com/ww/en/download/document/31007131K01000/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” chapter “Controler Memory Protection”: https://www.se.com/ww/en/download/document/EIO0000001999/
https://www.se.com/ww/en/download/document/31007131K01000/ - MitigationModicon MC80 Firmware Versions prior to SV2.1 installed on Modicon MC80 Controller (part numbers BMKC80)cisa_csaf_ot
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “MC80 Programmable Logic Controller(PLC), User Manual” in the section “Access Control List (ACL)”: https://www.se.com/ww/en/download/document/EIO0000002071/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/
https://www.se.com/ww/en/download/document/EIO0000002071/ - MitigationModicon Momentum Unity M1E Processor Firmware Versions prior to SV2.80 installed on Modicon Momentum Unity M1E Processor Controller (171CBU*)cisa_csaf_ot
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Momentum for EcoStruxure™ Control Expert -171CBU78090, 171CBU98090, 171CBU98091 Processors, User Guide” in the section “Controlling Access”:https://www.se.com/ww/en/download/document/HRB44124/• Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”:https://www.se.com/ww/en/download/document/EIO0000001999/
https://www.se.com/ww/en/download/document/HRB44124/
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.8–8.3
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (12)
Betroffene Produkte und Versionsbereiche.
Advisories (1)
Hersteller- und Ökosystem-Meldungen dazu.
- ICSA-24-326-04Schneider Electric Modicon M340, MC80, and Momentum Unity M1E (Update B)2024-11-12icsa · cisa_csaf_otUS
Schneider Electric is aware of multiple vulnerabilities in its Modicon Controllers M340 / Momentum / MC80 products.Modicon PAC control and monitor industrial operations.Failure to apply the provided remediations/mitigations below may risk unauthorized access to the controller, which could result in the possibility of denial of service and loss of confidentiality, integrity of the controller.January 2026 Update: Remediation is now available for Modicon MC80.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (4)
Externe Belege — Patches, Meldungen, Analysen.
- https://download.schneider-electric.com/doc/SEVD-2024-317-03/SEVD-2024-317-03.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2024-8937cnnvd
- https://download.schneider-electric.com/doc/SEVD-2024-317-03/SEVD-2024-317-03.pdfenisa_euvd
- https://download.schneider-electric.com/doc/SEVD-2024-317-03/SEVD-2024-317-03.pdfnvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan