CVE-2024-8933

highPriorität · verfolgen · 0EPSS 0.003 · 23. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.30% (23rd) EPSS
CVSS 7.5 · high
Is it mine?
15 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-27

CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause retrieval of password hash that could lead to denial of service and loss of confidentiality and integrity of controllers. To be successful, the attacker needs to inject themself inside the logical network while a valid user uploads or downloads a project file into the controller.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenEcoStruxure™ Control Expertcisa_csaf_ot

    EcoStruxure™ Control Expert V16.2 HF003 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-and-firmware

    https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-and-firmware
  • BehobenModicon M340 CPU Firmware Versions prior to SV3.70 installed on Modicon M340 CPU Controller (part numbers BMXP34*)cisa_csaf_ot

    Version 3.70 of Modicon M340 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware

    https://www.se.com/ww/en/product-range/1468-modicon-m340/#software-and-firmware
  • BehobenModicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90 installed on Modicon Momentum Unity M1E Processor Controller (171CBU*)cisa_csaf_ot

    Firmware SV2.90 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/535-modicon-momentum/#software-and-firmware Important: Customer needs to use version of EcoStruxure™ Control Expert v16.2 HF003 minimum to connect with the latest version of Modicon Momentum.

    https://www.se.com/ww/en/product-range/535-modicon-momentum/#software-and-firmware
  • MitigationEcoStruxure™ Control Expertcisa_csaf_ot

    Customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Momentum for EcoStruxure™ Control Expert - 171CBU78090, 171CBU98090, 171CBU98091 Processors, User Guide” in the section “Controlling Access”: https://www.se.com/ww/en/download/document/HRB44124/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/

    https://www.se.com/ww/en/download/document/HRB44124/
  • MitigationModicon M340 CPU Firmware Versions prior to SV3.70 installed on Modicon M340 CPU Controller (part numbers BMXP34*)cisa_csaf_ot

    Customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M340 for Ethernet Communications Modules and Processors User Manual” in chapter “Messaging Configuration Parameters”: https://www.se.com/ww/en/download/document/31007131K01000/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” chapter “Controler Memory Protection”: https://www.se.com/ww/en/download/document/EIO0000001999/

    https://www.se.com/ww/en/download/document/31007131K01000/
  • MitigationModicon MC80 Firmware All Versions installed on Modicon MC80 Controller (part numbers BMKC80)cisa_csaf_ot

    Schneider Electric is establishing a remediation plan for all future versions of Modicon MC80 that will include a fix for CVE-2024-8933. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “MC80 Programmable Logic Controller(PLC), User Manual” in the section “Access Control List (ACL)”: https://www.se.com/ww/en/download/document/EIO0000002071/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/

    https://www.se.com/ww/en/download/document/EIO0000002071/
  • MitigationModicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90 installed on Modicon Momentum Unity M1E Processor Controller (171CBU*)cisa_csaf_ot

    Customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Momentum for EcoStruxure™ Control Expert - 171CBU78090, 171CBU98090, 171CBU98091 Processors, User Guide” in the section “Controlling Access”: https://www.se.com/ww/en/download/document/HRB44124/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to “Modicon Controller Systems Cybersecurity, User Guide”: https://www.se.com/ww/en/download/document/EIO0000001999/

    https://www.se.com/ww/en/download/document/HRB44124/
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.8–7.5

v3.17.5highCVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · cybersecurity@se.comAusnutzbarkeit 1.6 · Auswirkung 5.9
v4.07.5highCVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.07.5highCVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.04.8mediumCVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (15)

Betroffene Produkte und Versionsbereiche.

06

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-24-326-03Schneider Electric Modicon M340, MC80, and Momentum Unity M1E & EcoStruxure (Update A)2024-11-12icsa · cisa_csaf_otUS

    Schneider Electric is aware of multiple vulnerabilities in its Modicon Controllers M340 / Momentum / MC80 / EcoStruxure™ Control Expert products. [Modicon PAC](https://www.se.com/ww/en/product-subcategory/3950-pac-programmable-automation-controllers/?filter=business-1-industrial-automation-and-control) products control and monitor industrial operations. [EcoStruxure™ Control Expert](https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#overview) is the engineering application for Modicon Controllers. Failure to apply the provided remediations/mitigations below may risk unauthorized access to the controller, which could result in the possibility of denial of service and loss of confidentiality, integrity of the controller.

07

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2024-11-13geändert 2026-06-17
09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan