CVE-2024-6242

highPriorität · verfolgen · 4EPSS 0.111 · 96. PerzentilDEEURUUS
grimoire priorityP1 · Urgent
Exploitable?
—
no known exploitation
Likely / severe?
11.1% (96th) EPSS
CVSS 8.4 · high
Is it mine?
65 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-26

A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • Behoben1756-EN4TRcisa_csaf_ot

    1756-EN4TR: Update to versions V5.001 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
  • BehobenControlLogix 5580 (1756-L8z)cisa_csaf_ot

    ControlLogix 5580 (1756-L8z): Update to versions V32.016, V33.015, V34.014,V35.011 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
  • Mitigation1756-EN2F, Series A/B (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series A/B (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series Ccisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series Dcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TP, Series Acisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series Ccisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series Bcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN4TRcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationControlLogix 5580 (1756-L8z)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationGuardLogix 5580 (1756-L8zS)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.4
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.5–8.4

v3.18.4highCVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:C/C:L/I:H/A:Hsecondary · CISA US
v3.18.4highAV:N/AC:H/PR:L/UI:N/S:C/C:L/I:H/A:Hsecondary · FSTEC (BDU) RU
v4.07.3highCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:Hsecondary · ENISA EU
v4.07.3highCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · PSIRT@rockwellautomation.com
v4.04.5mediumCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (65)

Betroffene Produkte und Versionsbereiche.

20 von 65 angezeigt
06

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • WID-SEC-W-2024-1747Rockwell Automation ControlLogix: Schwachstelle ermöglicht Umgehen von SicherheitsvorkehrungenDeutsch2024-08-01csaf · cert_bundDE

    Ein entfernter, authentisierter Angreifer kann eine Schwachstelle in Rockwell Automation ControlLogix ausnutzen, um Sicherheitsvorkehrungen zu umgehen.

  • ICSA-24-214-09Rockwell Automation Logix Controllers2024-08-01icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability could allow an attacker to execute CIP programming and configuration commands.

07

auch bekannt als (5)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2024-08-01geändert 2026-06-17
09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan