CVE-2024-53832
mediumPriorität · verfolgen · 0EPSS 0.003 · 21. PerzentilDEEUNLUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V05.30). The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- BehobenCPCI85 Central Processing/Communicationsiemens_psirt
Update to V05.30 or later version
- BehobenCPCI85 Central Processing/Communicationcisa_csaf_ot
Update to V05.30 or later version
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · low–medium · 1.7–5.1
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (7)
Betroffene Produkte und Versionsbereiche.
- cpci85_central_processing_communicationalle Versionenncsc_nlNLcpe:2.3:a:siemens:cpci85_central_processing_communication:*:*:*:*:*:*:*:*
Advisories (4)
Hersteller- und Ökosystem-Meldungen dazu.
- NCSC-2024-0473Kwetsbaarheden verholpen in Siemens productenNL2024-12-10csaf · ncsc_nlNL
Siemens heeft kwetsbaarheden verholpen in diverse producten als COMOS, RUGGEDCOM, SENTRON, SICAM, SIMATIC en TeamCenter.
- SSA-128393SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-80502024-12-10csaf · siemens_psirtDE
The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware. Siemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions. Both the firmware and the hardware update are required to fix the vulnerability. For details see the section "Additional Information".
- WID-SEC-W-2024-3655Siemens SICAM: Schwachstelle ermöglicht Offenlegung von InformationenDeutsch2024-12-10csaf · cert_bundDE
Ein Angreifer mit physischem Zugriff kann eine Schwachstelle in Siemens SICAM ausnutzen, um Informationen offenzulegen.
- ICSA-24-347-01Siemens CPCI85 Central Processing/Communication 2024-12-10icsa · cisa_csaf_otUS
The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware. Siemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions. Both the firmware and the hardware update are required to fix the vulnerability. For details see the section "Additional Information".