CVE-2024-37998

criticalPriorität · verfolgen · 0EPSS 0.005 · 39. PerzentilDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.45% (39th) EPSS
CVSS 9.8 · critical
Is it mine?
12 products
Prüfe deine Angriffsfläche
Who says so?
6 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-26

A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.40), SICORE Base system (All versions < V1.4.0). The password of administrative accounts of the affected applications can be reset without requiring the knowledge of the current password, given the auto login is enabled. This could allow an unauthorized attacker to obtain administrative access of the affected applications.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenCPCI85 Central Processing/Communicationsiemens_psirt

    Update to V5.40 or later version The firmware CPCI85 V5.40 is present within “CP-8031/CP-8050 Package” V5.40

  • BehobenSICORE Base systemsiemens_psirt

    Update to V1.4.0 or later version The firmware SICORE V1.4.0 is present within “SICAM 8 Software Solution Package” V5.40

  • BehobenCPCI85 Central Processing/Communicationcisa_csaf_ot

    Update to V5.40 or later version The firmware CPCI85 V5.40 is present within “CP-8031/CP-8050 Package” V5.40

  • BehobenSICORE Base systemcisa_csaf_ot

    Update to V1.4.0 or later version The firmware SICORE V1.4.0 is present within “SICAM 8 Software Solution Package” V5.40

  • MitigationCPCI85 Central Processing/Communicationsiemens_psirt

    Disable the auto login feature

  • MitigationSICORE Base systemsiemens_psirt

    Disable the auto login feature

  • MitigationCPCI85 Central Processing/Communicationcisa_csaf_ot

    Disable the auto login feature

  • MitigationSICORE Base systemcisa_csaf_ot

    Disable the auto login feature

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 8.1–9.8

v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · productcert@siemens.com DEAusnutzbarkeit 3.9 · Auswirkung 5.9
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · Siemens ProductCERT DE
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.1highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (12)

Betroffene Produkte und Versionsbereiche.

06

Advisories (3)

Hersteller- und Ökosystem-Meldungen dazu.

  • SSA-071402SSA-071402: Multiple Vulnerabilities in SICAM Products2024-07-22csaf · siemens_psirtDE

    Multiple SICAM products are affected by unauthorized password reset and firmware downgrade vulnerabilities that could lead to privilege escalation and potential leak of information, namely: - SICAM A8000 Device firmware - CPCI85 for CP-8031/CP-8050 - SICAM EGS Device firmware - CPCI85 - SICAM 8 Software Solution - SICORE Siemens has released new firmware versions for the affected products and recommends to update to the latest versions.

  • WID-SEC-W-2024-1686Siemens SICAM: Mehrere SchwachstellenDeutsch2024-07-22csaf · cert_bundDE

    Ein Angreifer kann mehrere Schwachstellen in Siemens SICAM ausnutzen, um seine Privilegien zu erhöhen oder die Firmware-Version herabzustufen.

  • ICSA-24-207-01Siemens SICAM Products2024-07-22icsa · cisa_csaf_otUS

    Multiple SICAM products are affected by unauthorized password reset and firmware downgrade vulnerabilities that could lead to privilege escalation and potential leak of information, namely: - SICAM A8000 Device firmware - CPCI85 for CP-8031/CP-8050 - SICAM EGS Device firmware - CPCI85 - SICAM 8 Software Solution - SICORE Siemens has released new firmware versions for the affected products and recommends to update to the latest versions.