CVE-2024-12703

highPriorität · verfolgen · 0EPSS 0.003 · 23. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.31% (23rd) EPSS
CVSS 7.8 · high
Is it mine?
8 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-29

CWE-502: Deserialization of untrusted data vulnerability exists that could lead to loss of confidentiality, integrity and potential remote code execution on workstation when a non-admin authenticated user opens a malicious project file.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenRemoteConnect and SCADAPack™ x70 Utilities - RemoteConnectcisa_csaf_ot

    Version R3.4.2 RemoteConnect configuration software includes a fix for this vulnerability and is available for download here:https://www.se.com/ww/en/download/document/RemoteConnect/

    https://www.se.com/ww/en/download/document/RemoteConnect/
  • MitigationRemoteConnect and SCADAPack™ x70 Utilities - RemoteConnectcisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: Schneider Electric is establishing a remediation plan for all future versions of Security Administrator configuration software that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit:• Only open project files received from a trusted source. • Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage.• Encrypt project file when stored and restrict the access to only trusted users. • When exchanging files over the network, use secure communication protocols. • Follow the SCADAPack™ Security Guidelines

    https://www.se.com/ww/en/download/document/SCADAPack_Cybersecurity_Guide/
  • MitigationRemoteConnect and SCADAPack™ x70 Utilities - Security Administratorcisa_csaf_ot

    Schneider Electric is establishing a remediation plan for all future versions of Security Administrator configuration software that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit:• Only open project files received from a trusted source. • Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage.• Encrypt project file when stored and restrict the access to only trusted users. • When exchanging files over the network, use secure communication protocols. • Follow the SCADAPack™ Security Guidelines

    https://www.se.com/ww/en/download/document/SCADAPack_Cybersecurity_Guide/
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.9–8.5

v3.17.8highCVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.17.8highAV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.17.8highCVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:Hsecondary · cybersecurity@se.comAusnutzbarkeit 1.8 · Auswirkung 5.9
v4.08.5highCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.5highCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.05.9mediumCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (8)

Betroffene Produkte und Versionsbereiche.

06

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-25-028-06Schneider Electric RemoteConnect and SCADAPack x70 Utilities (Update A)2025-01-14icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its RemoteConnect and SCADAPack™ x70 Utilities software product. The RemoteConnect and SCADAPack™ x70 Utilities https://www.se.com/ww/en/product-category/6000-telemetry-and-remote-scada-systems/ product is a configuration software providing a user interface that allows users to configure and manage communications and operations for SCADAPack™ x70 devices. Failure to apply the Mitigations provided below may risk deserialization of untrusted data, which could result in loss of confidentiality, integrity and potential remote code execution on the compromised workstation.

07

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2025-01-17geändert 2026-06-17
09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan