CVE-2023-28829

highPriorität · verfolgen · 35EPSS 0.003 · 22. PerzentilDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.29% (22nd) EPSS
CVSS 8.8 · high
Is it mine?
42 products
Prüfe deine Angriffsfläche
Who says so?
6 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-27

A vulnerability has been identified in SIMATIC NET PC Software V14 (All versions), SIMATIC NET PC Software V15 (All versions), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions), SIMATIC PCS 7 V9.1 (All versions), SIMATIC WinCC (All versions < V8.0), SINAUT Software ST7sc (All versions). Before SIMATIC WinCC V8, legacy OPC services (OPC DA (Data Access), OPC HDA (Historical Data Access), and OPC AE (Alarms & Events)) were used per default. These services were designed on top of the Windows ActiveX and DCOM mechanisms and do not implement state-of-the-art security mechanisms for authentication and encryption of contents.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenSIMATIC WinCCsiemens_psirt

    Update to V8.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109816599/
  • BehobenSIMATIC WinCCcisa_csaf_ot

    Update to V8.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109816599/
  • MitigationSIMATIC NET PC Software V14siemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC NET PC Software V15siemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V8.2siemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V9.0siemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V9.1siemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC WinCCsiemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSINAUT Software ST7scsiemens_psirt

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC NET PC Software V14cisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC NET PC Software V15cisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V8.2cisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V9.0cisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC PCS 7 V9.1cisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSIMATIC WinCCcisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • MitigationSINAUT Software ST7sccisa_csaf_ot

    Disable the legacy OPC DA/HDA/AE services and switch to OPC UA, if possible

  • WorkaroundSIMATIC NET PC Software V14siemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC NET PC Software V15siemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V8.2siemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V9.0siemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V9.1siemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC WinCCsiemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSINAUT Software ST7scsiemens_psirt

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC NET PC Software V14cisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC NET PC Software V15cisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V8.2cisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V9.0cisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC PCS 7 V9.1cisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSIMATIC WinCCcisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • WorkaroundSINAUT Software ST7sccisa_csaf_ot

    SINATIC NET PC Software: Ensure that only trusted users are part of the SIMATIC Net group

  • Kein Fix geplantSIMATIC NET PC Software V14siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC NET PC Software V15siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V8.2siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V9.0siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V9.1siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSINAUT Software ST7scsiemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC NET PC Software V14cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC NET PC Software V15cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V8.2cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V9.0cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7 V9.1cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSINAUT Software ST7sccisa_csaf_ot

    Currently no fix is planned

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · low–high · 3.9–8.8

v3.18.8highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hprimary · NVD / NIST USAusnutzbarkeit 2.8 · Auswirkung 5.9
v3.13.9lowCVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:L/E:P/RL:O/RC:Csecondary · CISA US
v3.13.9lowAV:A/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:Lsecondary · FSTEC (BDU) RU
v3.13.9lowCVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:L/E:P/RL:O/RC:Csecondary · ENISA EU
v3.13.9lowCVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:Lsecondary · productcert@siemens.com DEAusnutzbarkeit 0.5 · Auswirkung 3.4
v3.13.9lowCVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:L/I:L/A:L/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
v3.18.1highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Trackcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (42)

Betroffene Produkte und Versionsbereiche.

06

Advisories (3)

Hersteller- und Ökosystem-Meldungen dazu.

  • SSA-508677SSA-508677: Use of Obsolete Function Vulnerability in SIMATIC WinCC before V82023-06-13csaf · siemens_psirtDE

    Before SIMATIC WinCC V8, legacy OPC services (OPC DA (Data Access), OPC HDA (Historical Data Access), and OPC AE (Alarms & Events)) were used per default. These services were designed on top of the Windows ActiveX and DCOM mechanisms and do not implement state-of-the-art security mechanisms for authentication and encryption of contents. Starting with WinCC V8.0 the legacy OPC services are no longer enabled by default in new installations. Siemens recommends to use OPC UA instead and to disable the legacy OPC services. For deployments where the legacy OPC services are still in use, ensure that only trusted users are part of the SIMATIC HMI group.

  • WID-SEC-W-2023-1427Siemens SIMATIC WinCC: Mehrere SchwachstellenDeutsch2023-06-12csaf · cert_bundDE

    Ein Angreifer kann mehrere Schwachstellen in Siemens SIMATIC WinCC ausnutzen, um Sicherheitsvorkehrungen zu umgehen und seine Rechte zu erweitern.

  • ICSA-23-166-05Siemens SIMATIC WinCC2023-06-13icsa · cisa_csaf_otUS

    Before SIMATIC WinCC V8, legacy OPC services (OPC DA (Data Access), OPC HDA (Historical Data Access), and OPC AE (Alarms & Events)) were used per default. These services were designed on top of the Windows ActiveX and DCOM mechanisms and do not implement state-of-the-art security mechanisms for authentication and encryption of contents. Starting with WinCC V8.0 the legacy OPC services are no longer enabled by default in new installations. Siemens recommends to use OPC UA instead and to disable the legacy OPC services. For deployments where the legacy OPC services are still in use, ensure that only trusted users are part of the SIMATIC HMI group.