CVE-2022-32140

mediumPriorität · verfolgen · 16EPSS 0.011 · 65. PerzentilDEEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.06% (65th) EPSS
CVSS 4 · medium
Is it mine?
41 products
Prüfe deine Angriffsfläche
Who says so?
7 sources
cnnvd · enisa_euvd · cisa_csaf_ot · festo_psirt

EPSS · bewertet 2026-10-27

Multiple CODESYS products are affected to a buffer overflow.A low privileged remote attacker may craft a request, which can cause a buffer copy without checking the size of the service, resulting in a denial-of-service condition. User Interaction is not required.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • Behobenwago_psirt

    WAGO recommends that all affected users with WAGO I/O-PRO/CODESYS 2.3 PLCs update to the firmware and use the latest version of WAGO I/O-Pro as soon as it is available. Until the updates are available, we recommend switching off the CODESYS IP port 2455 after commissioning or, if this not possible, use a strong admin password. ### PFC200 Family | Ord. No. | Firmware | |-----------------------|----------------------------------| | 750-8202/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8203/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8204/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8206/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8207/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8208/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8210/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8211/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8212/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8213/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8214/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8216/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-8217/xxx-xxx | UPDATE B: Available in Q1 2024 | ### Ethernet Controller 4th Generation Family – UPDATE B | Ord. No. | Firmware | |-----------------------|----------------------------------| | 750-823 | UPDATE B: Available in Q1 2024 | | 750-332 | UPDATE B: Available in Q1 2024 | | 750-832/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-862 | UPDATE B: Available in Q1 2024 | | 750-890/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-891 | UPDATE B: Available in Q1 2024 | | 750-893 | UPDATE B: Available in Q1 2024 | ### Ethernet Controller 3rd Generation Family – UPDATE B | Ord. No. | Firmware | |-----------------------|----------------------------------| | 750-331 | UPDATE B: Available in Q1 2024 | | 750-829 | UPDATE B: Available in Q1 2024 | | 750-831/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-852 | UPDATE B: Available in Q1 2024 | | 750-880/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-881 | UPDATE B: Available in Q1 2024 | | 750-882 | UPDATE B: Available in Q1 2024 | | 750-885/xxx-xxx | UPDATE B: Available in Q1 2024 | | 750-889 | UPDATE B: Available in Q1 2024 | ### Engineering Software | Name | Firmware | |------------------|----------------------------------| | WAGO-I/O-PRO 32 | UPDATE B: Available in Q1 2024 |

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • Mitigationwago_psirt

    For vulnerabilities CVE-2022-1965, CVE-2022-32136, CVE-2022-32137, CVE-2022-32138, CVE-2022-32139, CVE-2022-32140, CVE-2022-32141, CVE-2022-32142, CVE-2022-32143 (CODESYS Advisory 2022-11): - Activation of online user management, to prevent unallowed actions from unauthorized attackers - Setting strong passwords - Use e!Runtime or CODESYS V3 For vulnerabilities CVE-2022-31805, CVE-2022-31806 (CODESYS Advisory 2022-12): - Activation of online user management, to prevent unallowed actions from unauthorized attackers - Use encryption of online communication whenever possible, this protects password transmission.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

6.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen

v2.04mediumAV:N/AC:L/Au:S/C:N/I:N/A:Pprimary · NVD / NIST USAusnutzbarkeit 8 · Auswirkung 2.9
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:Hsecondary · info@cert.vde.comAusnutzbarkeit 2.8 · Auswirkung 3.6
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:Hsecondary · WAGO PSIRT DE
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:Hsecondary · Festo PSIRT DE
v3.16mediumCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (41)

Betroffene Produkte und Versionsbereiche.

20 von 41 angezeigt
05

Advisories (4)

Hersteller- und Ökosystem-Meldungen dazu.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2022-040WAGO: Multiple Vulnerabilities in Controller with WAGO I/O-Pro / CODESYS 2.3 Runtime2022-10-17csaf · wago_psirtDE

    UPDATE A: Solution has updated release datesUPDATE B: Solution has updated release datesThis Advisory is published with reference to: CODESYS Advisory 2022-11 (Security update for CODESYS Control V2) CODESYS Advisory 2022-12 (Security update for CODESYS V2 password transport) CODESYS Advisory 2022-13 (Security update for CODESYS Gateway V2)

  • WID-SEC-W-2023-0825ABB AC-500: Mehrere SchwachstellenDeutsch2023-04-02csaf · cert_bundDE

    Ein entfernter, anonymer Angreifer kann mehrere Schwachstellen in ABB AC-500 ausnutzen, um beliebigen Programmcode auszuführen, Informationen offenzulegen, einen Denial of Service Zustand herbeizuführen oder Dateien zu manipulieren.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

08

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan