CVE-2022-31205
highPriorität · verfolgen · 30OT-Risiko · erhöhtEPSS 0.007 · 52. PerzentilEURUUSEPSS · bewertet 2026-10-27
In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Noch kein Hersteller-Fix; eine Mitigation ist verfügbar.
- MitigationCP1W-CIF41cisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CJ2Hcisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CJ2Mcisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CP1E/CP1Hcisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CP1Lcisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CS1H/CJ1Gcisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC CX-Programmercisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
- MitigationSYSMAC NJ/NX Seriescisa_csaf_ot
For CVE-2022-31205: Omron recommends using different passwords between the CP1W-CIF41 Ethernet Option Board and CP1 PLC itself. The Web UI password will not grant access to the PLC.
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.5–7.5
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (25)
Betroffene Produkte und Versionsbereiche.
Advisories (1)
Hersteller- und Ökosystem-Meldungen dazu.
- ICSA-22-179-02Omron SYSMAC CS/CJ/CP Series and NJ/NX Series2022-06-28icsa · cisa_csaf_otUS
Successful exploitation of these vulnerabilities could cause a denial-of-service condition and allow remote code execution.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (11)
Externe Belege — Patches, Meldungen, Analysen.
- https://automation.omron.com/en/us/Patchcnnvd
- https://cxsecurity.com/cveshow/CVE-2022-31205/cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-179-02cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.3140cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022062925cnnvd
- https://www.forescout.com/blog/cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02enisa_euvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.