CVE-2021-42029
highPriorität · verfolgen · 31EPSS 0.002 · 15. PerzentilDEEURUUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) V15 (All versions), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 5), SIMATIC STEP 7 (TIA Portal) V17 (All versions < V17 Update 2). An attacker could achieve privilege escalation on the web server of certain devices due to improper access control vulnerability in the engineering system software. The attacker needs to have direct access to the impacted web server.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- BehobenSIMATIC STEP 7 (TIA Portal) V16siemens_psirt
Update to V16 Update 5 or later version
https://support.industry.siemens.com/cs/gb/en/view/109775861/ - BehobenSIMATIC STEP 7 (TIA Portal) V17siemens_psirt
Update to V17 Update 2 or later version
https://support.industry.siemens.com/cs/gb/en/view/109784441/ - BehobenSIMATIC STEP 7 (TIA Portal) V16cisa_csaf_ot
Update to V16 Update 5 or later version
https://support.industry.siemens.com/cs/gb/en/view/109775861/ - BehobenSIMATIC STEP 7 (TIA Portal) V17cisa_csaf_ot
Update to V17 Update 2 or later version
https://support.industry.siemens.com/cs/gb/en/view/109784441/ - MitigationSIMATIC STEP 7 (TIA Portal) V15siemens_psirt
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- MitigationSIMATIC STEP 7 (TIA Portal) V16siemens_psirt
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- MitigationSIMATIC STEP 7 (TIA Portal) V17siemens_psirt
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- MitigationSIMATIC STEP 7 (TIA Portal) V15cisa_csaf_ot
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- MitigationSIMATIC STEP 7 (TIA Portal) V16cisa_csaf_ot
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- MitigationSIMATIC STEP 7 (TIA Portal) V17cisa_csaf_ot
In case a new TIA-Portal version is not available, updating the web server's user configuration is not effective in this situation. Instead - the PLC must be deleted and reconfigured with a new project. WARNING: The PLC-program should be copied before deleting the PLC. Or - the original project (one that was not uploaded by a PLC) should be used to update the web server's user management and to download the changed configuration
- Kein Fix geplantSIMATIC STEP 7 (TIA Portal) V15siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC STEP 7 (TIA Portal) V15cisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.4–7.8
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (18)
Betroffene Produkte und Versionsbereiche.
Advisories (2)
Hersteller- und Ökosystem-Meldungen dazu.
- SSA-350757SSA-350757: Improper Access Control Vulnerability in TIA Portal Affecting S7-1200 and S7-1500 CPUs Web Server (Incl. Related ET200 CPUs and SIPLUS variants)2022-04-12csaf · siemens_psirtDE
An attacker could achieve privilege escalation on the web server of certain devices configured by SIMATIC STEP 7 (TIA Portal) due to incorrect handling of the webserver's user management configuration during downloading. This only affects the S7-1200 and S7-1500 CPUs' (incl. related ET200 CPUs and SIPLUS variants) web server, when activated. Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
- ICSA-22-104-14Siemens SIMATIC STEP 7 (TIA Portal)2022-04-12icsa · cisa_csaf_otUS
An attacker could achieve privilege escalation on the web server of certain devices configured by SIMATIC STEP 7 (TIA Portal) due to incorrect handling of the webserver's user management configuration during downloading. This only affects the S7-1200 and S7-1500 CPUs' (incl. related ET200 CPUs and SIPLUS variants) web server, when activated. Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (7)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/pdf/ssa-350757.pdfcnnvd
- https://cxsecurity.com/cveshow/CVE-2021-42029/cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-104-14cnnvd
- https://vigilance.fr/vulnerability/SIMATIC-privilege-escalation-via-TIA-Portal-38017cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022042135cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-350757.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-350757.pdfPatchVendor Advisorynvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan