CVE-2021-40368
mediumPriorität · verfolgen · 20EPSS 0.010 · 63. PerzentilDEEURUUSEPSS · bewertet 2026-10-23
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions < V10.1), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions < V8.2.3), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- Behoben SIMATIC S7-400 CPU 412-2 PN/DP V7 (6ES7412-2EK07-0AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - BehobenSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)siemens_psirt
Update to V6.0.10 or later version
https://support.industry.siemens.com/cs/ww/en/view/109474550/ - BehobenSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)siemens_psirt
Update to V10.1 or later version To obtain SIMATIC S7-410 V10.1 contact your local support.
- BehobenSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)siemens_psirt
Update to V8.2.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109476571/ - BehobenSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - BehobenSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)siemens_psirt
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 412-2 PN/DP V7 (6ES7412-2EK07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Behoben SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - BehobenSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Update to V6.0.10 or later version
https://support.industry.siemens.com/cs/ww/en/view/109474550/ - BehobenSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Update to V10.1 or later version To obtain SIMATIC S7-410 V10.1 contact your local support.
- BehobenSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Update to V8.2.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109476571/ - BehobenSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - BehobenSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)cisa_csaf_ot
Update to V7.0.3 or later version
https://support.industry.siemens.com/cs/ww/en/view/109752685/ - Mitigation SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 412-2 PN/DP V7 (6ES7412-2EK07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-3 DP V7 (6ES7414-3XM07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-2 DP V7 (6ES7416-2XP07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-3 DP V7 (6ES7416-3XS07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416F-2 DP V7 (6ES7416-2FP07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 417-4 DP V7 (6ES7417-4XT07-0AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 416-3 V7 (6AG1416-3XS07-7AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 417-4 V7 (6AG1417-4XT07-7AB0)siemens_psirt
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 412-2 PN/DP V7 (6ES7412-2EK07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-3 DP V7 (6ES7414-3XM07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-2 DP V7 (6ES7416-2XP07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-3 DP V7 (6ES7416-3XS07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416F-2 DP V7 (6ES7416-2FP07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Mitigation SIMATIC S7-400 CPU 417-4 DP V7 (6ES7417-4XT07-0AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 416-3 V7 (6AG1416-3XS07-7AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- MitigationSIPLUS S7-400 CPU 417-4 V7 (6AG1417-4XT07-7AB0)cisa_csaf_ot
Limit access to port 102/tcp to trusted users and systems only
- Kein Fix geplant SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 414-3 DP V7 (6ES7414-3XM07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416-2 DP V7 (6ES7416-2XP07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416-3 DP V7 (6ES7416-3XS07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416F-2 DP V7 (6ES7416-2FP07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 417-4 DP V7 (6ES7417-4XT07-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS S7-400 CPU 416-3 V7 (6AG1416-3XS07-7AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS S7-400 CPU 417-4 V7 (6AG1417-4XT07-7AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 414-3 DP V7 (6ES7414-3XM07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416-2 DP V7 (6ES7416-2XP07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416-3 DP V7 (6ES7416-3XS07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 416F-2 DP V7 (6ES7416-2FP07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplant SIMATIC S7-400 CPU 417-4 DP V7 (6ES7417-4XT07-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS S7-400 CPU 416-3 V7 (6AG1416-3XS07-7AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS S7-400 CPU 417-4 V7 (6AG1417-4XT07-7AB0)cisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.3–7.5
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (88)
Betroffene Produkte und Versionsbereiche.
Advisories (2)
Hersteller- und Ökosystem-Meldungen dazu.
- SSA-557541SSA-557541: Denial-of-Service Vulnerability in SIMATIC S7-400 CPUs2022-04-12csaf · siemens_psirtDE
SIMATIC S7-400 CPU devices contain an input validation vulnerability that could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations. Siemens has released an update for SIMATIC S7-410 V10 CPU family and SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants for both) and recommends to update to the latest version. Siemens is preparing further updates and recommends specific countermeasures for products where updates are not yet available.
- ICSA-22-104-12Siemens SIMATIC S7-4002022-04-12icsa · cisa_csaf_otUS
SIMATIC S7-400 CPU devices contain an input validation vulnerability that could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations. Siemens has released an update for SIMATIC S7-410 V10 CPU family and SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants for both) and recommends to update to the latest version. Siemens is preparing further updates and recommends specific countermeasures for products where updates are not yet available.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (8)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/pdf/ssa-557541.pdfcnnvd
- https://cxsecurity.com/cveshow/CVE-2021-40368/cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-104-12cnnvd
- https://vigilance.fr/vulnerability/SIMATIC-S7-400-denial-of-service-via-Port-102-tcp-38019cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.4031cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022042010cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-557541.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-557541.pdfPatchVendor Advisorynvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan