CVE-2021-34593

mediumPriorität · verfolgen · 21EPSS 0.027 · 86. PerzentilDEEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
2.66% (86th) EPSS
CVSS 5 · medium
Is it mine?
56 products
Prüfe deine Angriffsfläche
Who says so?
7 sources
cnnvd · enisa_euvd · cisa_csaf_ot · festo_psirt

EPSS · bewertet 2026-10-22

In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Noch kein Hersteller-Fix; eine Mitigation ist verfügbar.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • Mitigationwago_psirt

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the CODESYS 2.3 port 2455.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • Kein Fix verfügbarpilz_psirt

    PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures. • PMCprimo C2, PMCprimo MC: Installation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. The V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.

  • Kein Fix verfügbarPMC programming tool 2.x.xpilz_psirt

    No product-specific countermeasures available, please follow the general countermeasures or migrate your application to the CODESYS V3 runtime system.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.3–7.5

v2.05mediumAV:N/AC:L/Au:N/C:N/I:N/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 2.9
v2.04.3mediumAV:N/AC:L/Au:N/C:N/I:N/A:P/E:Usecondary · CVSS-BT (t0sche)
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · info@cert.vde.comAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · WAGO PSIRT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Pilz PSIRT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Festo PSIRT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 3.6
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (56)

Betroffene Produkte und Versionsbereiche.

20 von 56 angezeigt
05

Advisories (5)

Hersteller- und Ökosystem-Meldungen dazu.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2021-049WAGO: Denial of Service Vulnerability in CODESYS Runtime 2.32021-11-16csaf · wago_psirtDE

    A Denial-of-Service Vulnerability was reported in CODESYS 2.3 Runtime. The CODESYS 2.3 Runtime is an essential component in several WAGO PLC's. All vulnerable PLCs are listed in chapter 'Affected Products'.

  • VDE-2021-054Pilz: Multiple vulnerabilities in CODESYS V2 and V3 runtime system2022-04-26csaf · pilz_psirtDE

    Several Pilz products use Versions V2 and V3 of the CODESYS runtime system from CODESYS GmbH, which enables the execution of IEC 61131-3 PLC programs. These runtime environments contain several vulnerabilities, which an attacker can exploit via the network. Successful exploitation of the vulnerabilities results in reduced availability and, in a worst case, to the insertion of program code.

  • VDE-2021-055Pilz: PMC programming tool 2.x.x affected by multiple vulnerabilities2022-04-26csaf · pilz_psirtDE

    The software product PMC programming tool from Pilz is based on the software CODESYS Development System from CODESYS GmbH. This software is affected by several vulnerabilities, which an attacker can exploit locally or via the network. This means that, in a worst case, attackers could execute arbitrary program code on the PC on which the PMC programming tool is used.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

08

Referenzen (13)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan