CVE-2021-20093

mediumPriorität · beachten · 48EPSS 0.333 · 98. PerzentilDEEURUUS
grimoire priorityP1 · Urgent
Exploitable?
—
no known exploitation
Likely / severe?
33.3% (98th) EPSS
CVSS 6.4 · medium
Is it mine?
91 products
Prüfe deine Angriffsfläche
Who says so?
8 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-27

A buffer over-read vulnerability exists in Wibu-Systems CodeMeter versions < 7.21a. An unauthenticated remote attacker can exploit this issue to disclose heap memory contents or crash the CodeMeter Runtime Server.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenFieldEchosick_psirt

    Update to latest version

    https://www.sick.com/de/de/sick-integrationspace/software-for-integration/fieldecho/fieldechoc2ae/p/p597264
  • BehobenDesigo CC family V5.0siemens_psirt

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenDesigo CC family V5.1siemens_psirt

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenDesigo CC family V6siemens_psirt

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenSENTRON powermanagersiemens_psirt

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenPSS(R)CAPEsiemens_psirt

    CAPE 14 installations installed from material dated 2021-06-16 or later are not affected, as they contain a fixed version of CodeMeter Runtime.

  • BehobenSIMATIC Information Serversiemens_psirt

    Update SIMATIC PCS neo to V3.1 or later version

  • BehobenSIMATIC PCS neosiemens_psirt

    Update to V3.1 or later version

  • BehobenSIMATIC Process Historian (incl. Process Historian OPC UA Server)siemens_psirt

    Update SIMATIC PCS neo to V3.1 or later version

  • BehobenSIMATIC WinCC OA V3.17siemens_psirt

    Update to V3.17 P013 or later version

    https://www.winccoa.com/downloads/category/versions-patches.html
  • BehobenSIMATIC WinCC OA V3.18siemens_psirt

    Update to V3.18 P002 or later version

    https://www.winccoa.com/downloads/category/versions-patches.html
  • BehobenSIMIT Simulation Platformsiemens_psirt

    Alternatively, install WIBU Systems CodeMeter Runtime V7.21a or V7.30a manually to fix the issue: Download the package from https://www.wibu.com/us/support/user/downloads-user-software.html and follow the installation instructions from WIBU Systems.

    https://support.industry.siemens.com/cs/ww/en/view/109800638/
  • BehobenSINEC INSsiemens_psirt

    Alternatively, update CodeMeter Runtime to V7.21a: Download the package "CodeMeter User Runtime for Linux, version 7.21a, Driver-only" from the WIBU Systems User Software website. Install it on the system which runs SINEC INS by executing the following command: "sudo dpkg --force-depends --force-confnew -i codemeter-7.21.4611.501_amd64.deb"

    https://support.industry.siemens.com/cs/ww/en/view/109806100/
  • BehobenSINEMA Remote Connect Serversiemens_psirt

    Update to V3.0 SP2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109793790/
  • Behobene!COCKPIT engineering software installation bundleswago_psirt

    We strongly encourage e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) users to update WIBU-SYSTEMS Codemeter by installing the latest available stand-alone WIBU-SYSTEMS Codemeter Version. During the WIBU-SYSTEMS Codemeter installation process, refer to the recommended setup settings according to the WIBU-SYSTEMS advisories, a brief summary is provided in the chapter mitigation. Please check for updates and details that may not be included in this document. WAGO will provide updated e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) setup routines with the latest WIBU-SYSTEMS Codemeter version in Q4/2021.

  • Behobenendress_hauser_psirt

    Update the software application of the affected products: | # | Product Name | Fixed Version | |----------------------------------|-----------------------------------------------|-------------------| | SCE30B | | | | SCE31B | SupplyCare Enterprise | >= 3.5.1 | | SCE32B | | | | SFE100 | DeviceCare | >= 1.07.07 | | SFE500 | FieldCare | >= 2.17.00 | | SMT50 | | | | SMT70 | Field Xpert | >= 1.06.00 | | SMT77 | | | | MS20 | | | | MS21 | Field Data Manager | >= 1.6.3 | | Freeware for the | | | | Proline Promag W 800/5W8C | Proline Promag W 800 OPC/UA Connectivity Server | > V1.3.7926 | | via Endress+Hauser Download Portal | | |

  • BehobenPSS(R)CAPEcisa_csaf_ot

    CAPE 14 installations installed from material dated 2021-06-16 or later are not affected, as they contain a fixed version of CodeMeter Runtime.

  • BehobenSIMATIC Information Servercisa_csaf_ot

    Update SIMATIC PCS neo to V3.1 or later version

  • BehobenSIMATIC PCS neocisa_csaf_ot

    Update to V3.1 or later version

  • BehobenSIMATIC Process Historian (incl. Process Historian OPC UA Server)cisa_csaf_ot

    Update SIMATIC PCS neo to V3.1 or later version

  • BehobenSIMATIC WinCC OA V3.17cisa_csaf_ot

    Update to V3.17 P013 or later version

    https://www.winccoa.com/downloads/category/versions-patches.html
  • BehobenSIMATIC WinCC OA V3.18cisa_csaf_ot

    Update to V3.18 P002 or later version

    https://www.winccoa.com/downloads/category/versions-patches.html
  • BehobenSIMIT Simulation Platformcisa_csaf_ot

    Alternatively, install WIBU Systems CodeMeter Runtime V7.21a or V7.30a manually to fix the issue: Download the package from https://www.wibu.com/us/support/user/downloads-user-software.html and follow the installation instructions from WIBU Systems.

    https://support.industry.siemens.com/cs/ww/en/view/109800638/
  • BehobenSINEC INScisa_csaf_ot

    Alternatively, update CodeMeter Runtime to V7.21a: Download the package "CodeMeter User Runtime for Linux, version 7.21a, Driver-only" from the WIBU Systems User Software website. Install it on the system which runs SINEC INS by executing the following command: "sudo dpkg --force-depends --force-confnew -i codemeter-7.21.4611.501_amd64.deb"

    https://support.industry.siemens.com/cs/ww/en/view/109806100/
  • BehobenSINEMA Remote Connect Servercisa_csaf_ot

    Update to V3.0 SP2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109793790/
  • BehobenDesigo CC family V5.0cisa_csaf_ot

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenDesigo CC family V5.1cisa_csaf_ot

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenDesigo CC family V6cisa_csaf_ot

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • BehobenSENTRON powermanagercisa_csaf_ot

    Install the patch (available at https://support.industry.siemens.com/cs/ww/en/view/109825787/), which can be applied to all released versions

  • MitigationPSS(R)CAPEsiemens_psirt

    If CAPE 14 was initially installed using earlier material, install WIBU Systems CodeMeter Runtime V7.21a or V7.30a manually to fix the issue: Download the package from https://www.psscape.com/codemeter and install it the same way as documented for previous versions in the PSS CAPE 14 Installation Manual. Contact PSS(R)CAPE Support at psscape.support.energy@siemens.com if you need assistance with patching affected systems.

  • MitigationSICAM 230siemens_psirt

    Update SICAM 230 to V8.00 or later version. Then update CodeMeter Runtime to V7.21a or V7.30a: Download the package from: https://www.wibu.com/us/support/user/downloads-user-software.html. Install it on SICAM 230 systems according to the procedure documented in chapter 9.2 of the COPA-DATA Security Vulnerability Announcement 2021_1: https://www.copadata.com/fileadmin/user_upload/faq/files/CD_SVA_2021_1.pdf.

  • MitigationSIMATIC Information Serversiemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC PCS neosiemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC Process Historian (incl. Process Historian OPC UA Server)siemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC WinCC OA V3.17siemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running (for details refer to the updated security manual of WinCC OA).

  • MitigationSIMATIC WinCC OA V3.18siemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running (for details refer to the updated security manual of WinCC OA).

  • MitigationSINEC INSsiemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running. Note that this is the default configuration, which therefore limits the exploitability to local attacks only.

  • MitigationSINEMA Remote Connect Serversiemens_psirt

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running. Note that this is the default configuration, which therefore limits the exploitability to local attacks only.

  • Mitigationwago_psirt

    1. Use general security best practices to protect systems from local and network attacks. 2. Run CodeMeter as client only and use localhost as binding for the CodeMeter communication 3. With binding to localhost an attack is no longer possible via remote network connection. The network server is disabled by default. 4. If it is not possible to disable the network server, using a host-based firewall to restrict access to the CmLAN port can reduce the risk. 5. The CmWAN server is disabled by default. Please check if CmWAN is enabled and disable the feature if it is not needed. 6. Run the CmWAN server only behind a reverse proxy with user authentication to prevent attacks from unauthenticated users. 7. The risk of an unauthenticated attacker can be further reduced by using a host-based firewall that only allows the reverse proxy to access the CmWAN port. For further impact information and risk mitigation, please refer to the official WIBU-SYSTEMS Advisory Website at https://wibu.com/support/security-advisories.html

  • Mitigationendress_hauser_psirt

    All vulnerabilities have already been fixed in several CodeMeter versions. Endress+Hauser recommends to use CodeMeter version >=7.40b. The version is available at https://www.wibu.com/support. For the Operating System WIN 7 it's recommended to update the operating system, use/re-install the Endress+Hauser Software Application supporting the newer operating system and update Code Meter to version >= 7.40b.

  • MitigationPSS(R)CAPEcisa_csaf_ot

    If CAPE 14 was initially installed using earlier material, install WIBU Systems CodeMeter Runtime V7.21a or V7.30a manually to fix the issue: Download the package from https://www.psscape.com/codemeter and install it the same way as documented for previous versions in the PSS CAPE 14 Installation Manual. Contact PSS(R)CAPE Support at psscape.support.energy@siemens.com if you need assistance with patching affected systems.

  • MitigationSICAM 230cisa_csaf_ot

    Update SICAM 230 to V8.00 or later version. Then update CodeMeter Runtime to V7.21a or V7.30a: Download the package from: https://www.wibu.com/us/support/user/downloads-user-software.html. Install it on SICAM 230 systems according to the procedure documented in chapter 9.2 of the COPA-DATA Security Vulnerability Announcement 2021_1: https://www.copadata.com/fileadmin/user_upload/faq/files/CD_SVA_2021_1.pdf.

  • MitigationSIMATIC Information Servercisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC PCS neocisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC Process Historian (incl. Process Historian OPC UA Server)cisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running.

  • MitigationSIMATIC WinCC OA V3.17cisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running (for details refer to the updated security manual of WinCC OA).

  • MitigationSIMATIC WinCC OA V3.18cisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running (for details refer to the updated security manual of WinCC OA).

  • MitigationSINEC INScisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running. Note that this is the default configuration, which therefore limits the exploitability to local attacks only.

  • MitigationSINEMA Remote Connect Servercisa_csaf_ot

    Limit remote access to port 22350/tcp on systems where the Codemeter runtime network server is running. Note that this is the default configuration, which therefore limits the exploitability to local attacks only.

  • Kein Fix geplantSICAM 230siemens_psirt

    Currently no remediation is planned

  • Kein Fix geplantSICAM 230cisa_csaf_ot

    Currently no remediation is planned

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.1
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–critical · 6.4–9.1

v2.06.4mediumAV:N/AC:L/Au:N/C:P/I:N/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 4.9
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 5.2
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.19.1criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Hsecondary · WAGO PSIRT DE
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Hsecondary · SICK PSIRT DE
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Hsecondary · Endress+Hauser PSIRT DE
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (91)

Betroffene Produkte und Versionsbereiche.

05

Advisories (7)

Hersteller- und Ökosystem-Meldungen dazu.

  • SCA-2022-0001Vulnerability in SICK FieldEcho2022-02-17csaf · sick_psirtDE

    WIBU publicly released an advisory for the WIBU product “CodeMeter Runtime Network Server”. The advisory discloses a buffer over-read vulnerability that was found in the WIBU product “CodeMeter Runtime Network Server”. By default the network server functionality is disabled, however the SICK product “FieldEcho” may be vulnerable, if customers enables this. SICK has released a new FieldEcho version and recommends updating to the newest version. Since version 1.5.2 of SICK “FieldEcho”, customer can choose to use their own license server. If so, SICK advises to take action in accordance with the official WIBU Security Advisory.

  • SSA-625850SSA-625850: Multiple WIBU Systems CodeMeter Vulnerabilities Affecting the Desigo CC Product Family and SENTRON powermanager2023-11-14csaf · siemens_psirtDE

    Versions V5.0 through V7 of the Desigo CC product family (Desigo CC, Desigo CC Compact, Desigo CC Connect, Cerberus DMS), as well as the Desigo CC-based SENTRON powermanager, are affected by multiple vulnerabilities in the underlying third-party component WIBU Systems CodeMeter Runtime. Successful exploitation of these vulnerabilities could allow remote attackers to execute arbitrary code on the Desigo CC server, or create a denial of service condition. While all Desigo CC version lines V5.0, V5.1 and V6 are affected by all listed vulnerabilities, V7 is only affected by CVE-2023-3935. Siemens has released a patch to update the CodeMeter Runtime component and recommends to apply the patch on affected systems.

  • SSA-675303SSA-675303: WIBU Systems CodeMeter Runtime Vulnerabilities in Siemens Products2021-07-13csaf · siemens_psirtDE

    WIBU Systems published information about two vulnerabilities and an associated fix release version of CodeMeter Runtime, a product provided by WIBU Systems and used in several Siemens products for license management. The vulnerabilities are described in the section "Vulnerability Classification" below and got assigned the CVE IDs CVE-2021-20093 and CVE-2021-20094. Successful exploitation of these vulnerabilities could allow an attacker to read data from the heap of the CodeMeter Runtime network server, or crash the CodeMeter Runtime Server (i.e., CodeMeter.exe). Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.

  • VDE-2021-043WAGO: Vulnerable WIBU-SYSTEMS Codemeter installed through e!COCKPIT and WAGO-I/O-Pro2021-08-31csaf · wago_psirtDE

    Multiple vulnerabilities were reported in WIBU-SYSTEMS Codemeter. WIBU-SYSTEMS Codemeter is installed by default during e!COCKPIT and WAGO-I/O-Pro (CODESYS 2.3) installations. All currently existing e!COCKPIT installation bundles and WAGO-I/O-Pro (CODESYS 2.3) installation bundles with Version 2.3.9.46, 2.3.9.47, 2.3.9.49, 2.3.9.53, 2.3.9.55, 2.3.9.61 and 2.3.9.66 contain vulnerable versions of WIBU-SYSTEMS Codemeter.

  • VDE-2022-019Endress+Hauser: Multiple products utilizing vulnerable WIBU-SYSTEMS CodeMeter components2022-06-02csaf · endress_hauser_psirtDE

    For detailed information please refer to WIBU SYSTEMS original Advisories at https://wibu.com/support/security-advisories.html.

  • ICSA-21-210-02Wibu-Systems CodeMeter Runtime2021-07-13icsa · cisa_csaf_otUS

    WIBU Systems published information about two vulnerabilities and an associated fix release version of CodeMeter Runtime, a product provided by WIBU Systems and used in several Siemens products for license management. The vulnerabilities are described in the section "Vulnerability Classification" below and got assigned the CVE IDs CVE-2021-20093 and CVE-2021-20094. Successful exploitation of these vulnerabilities could allow an attacker to read data from the heap of the CodeMeter Runtime network server, or crash the CodeMeter Runtime Server (i.e., CodeMeter.exe). Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.

  • ICSA-23-320-03Siemens Desigo CC product family2023-11-14icsa · cisa_csaf_otUS

    Versions V5.0 through V7 of the Desigo CC product family (Desigo CC, Desigo CC Compact, Desigo CC Connect, Cerberus DMS), as well as the Desigo CC-based SENTRON powermanager, are affected by multiple vulnerabilities in the underlying third-party component WIBU Systems CodeMeter Runtime. Successful exploitation of these vulnerabilities could allow remote attackers to execute arbitrary code on the Desigo CC server, or create a denial of service condition. While all Desigo CC version lines V5.0, V5.1 and V6 are affected by all listed vulnerabilities, V7 is only affected by CVE-2023-3935. Siemens has released a patch to update the CodeMeter Runtime component and recommends to apply the patch on affected systems.

06

auch bekannt als (5)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (15)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan