CVE-2020-25236
mediumPriorität · verfolgen · 20EPSS 0.003 · 18. PerzentilDEEUUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CEo (6ED1052-2CC08-0BA1) (All versions), LOGO! 24RCE (6ED1052-1HB08-0BA1) (All versions), LOGO! 24RCEo (6ED1052-2HB08-0BA1) (All versions), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1) (All versions), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1) (All versions), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1) (All versions), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1) (All versions), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1) (All versions), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1) (All versions), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1) (All versions), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1) (All versions). The control logic (CL) the LOGO! 8 executes could be manipulated in a way that could cause the device executing the CL to improperly handle the manipulation and crash. After successful execution of the attack, the device needs to be manually reset.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Noch kein Hersteller-Fix; eine Mitigation ist verfügbar.
- MitigationLOGO! 12/24RCE (6ED1052-1MD08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 12/24RCEo (6ED1052-2MD08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 230RCE (6ED1052-1FB08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 230RCEo (6ED1052-2FB08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24CE (6ED1052-1CC08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24CEo (6ED1052-2CC08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24RCE (6ED1052-1HB08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24RCEo (6ED1052-2HB08-0BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1)siemens_psirt
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 12/24RCE (6ED1052-1MD08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 12/24RCEo (6ED1052-2MD08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 230RCE (6ED1052-1FB08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 230RCEo (6ED1052-2FB08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24CE (6ED1052-1CC08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24CEo (6ED1052-2CC08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24RCE (6ED1052-1HB08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationLOGO! 24RCEo (6ED1052-2HB08-0BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- MitigationSIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1)cisa_csaf_ot
Siemens recommends limiting the possibilities to execute untrusted code if possible.
- Kein Fix geplantLOGO! 12/24RCE (6ED1052-1MD08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 12/24RCEo (6ED1052-2MD08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 230RCE (6ED1052-1FB08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 230RCEo (6ED1052-2FB08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 24CE (6ED1052-1CC08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 24CEo (6ED1052-2CC08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 24RCE (6ED1052-1HB08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 24RCEo (6ED1052-2HB08-0BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1)siemens_psirt
Currently no fix is planned
- Kein Fix geplantLOGO! 12/24RCE (6ED1052-1MD08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 12/24RCEo (6ED1052-2MD08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 230RCE (6ED1052-1FB08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 230RCEo (6ED1052-2FB08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 24CE (6ED1052-1CC08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 24CEo (6ED1052-2CC08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 24RCE (6ED1052-1HB08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantLOGO! 24RCEo (6ED1052-2HB08-0BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1)cisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (65)
Betroffene Produkte und Versionsbereiche.
Advisories (2)
Hersteller- und Ökosystem-Meldungen dazu.
- SSA-783481SSA-783481: Denial-of-Service Vulnerability in LOGO! 8 BM2021-03-09csaf · siemens_psirtDE
A Denial-of-Service vulnerability has been identified in LOGO! 8 BM. This vulnerability could allow an attacker to crash a device, if a user is tricked into loading a malicious project file onto an affected device. The vulnerability is related to the hardware of the product. Siemens has released new hardware versions with the LOGO! V8.4 BM and the SIPLUS LOGO! V8.4 BM product families for all affected devices in which this vulnerability is fixed. See the chapter "Additional Information" below for more details. For more information please also refer to the related product support article: https://support.industry.siemens.com/cs/ww/en/view/109826554/.
- ICSA-21-068-05Siemens LOGO! 8 BM2021-03-09icsa · cisa_csaf_otUS
A Denial-of-Service vulnerability has been identified in LOGO! 8 BM. This vulnerability could allow an attacker to crash a device, if a user is tricked into loading a malicious project file onto an affected device. The vulnerability is related to the hardware of the product. Siemens has released new hardware versions with the LOGO! V8.4 BM and the SIPLUS LOGO! V8.4 BM product families for all affected devices in which this vulnerability is fixed. See the chapter "Additional Information" below for more details. For more information please also refer to the related product support article: https://support.industry.siemens.com/cs/ww/en/view/109826554/.
auch bekannt als (3)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (9)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/html/ssa-783481.htmlcnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-783481.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2020-25236cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-21-068-05cnnvd
- https://www.auscert.org.au/bulletins/ESB-2021.0851cnnvd
- https://cert-portal.siemens.com/productcert/html/ssa-783481.htmlenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-783481.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/html/ssa-783481.htmlnvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.