CVE-2020-15783
highPriorität · verfolgen · 31EPSS 0.017 · 77. PerzentilDEEUUSEPSS · bewertet 2026-10-26
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC TDC CPU555 (All versions), SINUMERIK 840D sl (All versions). Sending multiple specially crafted packets to the affected devices could cause a Denial-of-Service on port 102. A cold restart is required to recover the service.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Noch kein Hersteller-Fix; eine Mitigation ist verfügbar.
- MitigationSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)siemens_psirt
Protect network access to port 102/tcp of affected devices.
- MitigationSIMATIC TDC CPU555siemens_psirt
Protect network access to port 102/tcp of affected devices.
- MitigationSINUMERIK 840D slsiemens_psirt
Protect network access to port 102/tcp of affected devices.
- MitigationSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot
Protect network access to port 102/tcp of affected devices.
- MitigationSIMATIC TDC CPU555cisa_csaf_ot
Protect network access to port 102/tcp of affected devices.
- MitigationSINUMERIK 840D slcisa_csaf_ot
Protect network access to port 102/tcp of affected devices.
- Kein Fix geplantSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC TDC CPU555siemens_psirt
Currently no fix is planned
- Kein Fix geplantSINUMERIK 840D slsiemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC TDC CPU555cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSINUMERIK 840D slcisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.9–7.8
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (24)
Betroffene Produkte und Versionsbereiche.
- siemens simatic s7-300 cpu 312 firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_312_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 314 firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_314_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 315-2 dp firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_315-2_dp_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 315-2 pn firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_315-2_pn_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 315f-2 dp firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_315f-2_dp_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 315f-2 pn firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_315f-2_pn_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 317-2 dp firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_317-2_dp_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 317-2 pn firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_317-2_pn_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 317f-2 dp firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_317f-2_dp_firmware:*:*:*:*:*:*:*:*
- siemens simatic s7-300 cpu 317f-2 pn firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_s7-300_cpu_317f-2_pn_firmware:*:*:*:*:*:*:*:*
- siemens simatic tdc cpu555 firmwarealle VersionennvdUScpe:2.3:o:siemens:simatic_tdc_cpu555_firmware:*:*:*:*:*:*:*:*
Advisories (2)
Hersteller- und Ökosystem-Meldungen dazu.
- SSA-492828SSA-492828: Denial-of-Service Vulnerability in SIMATIC S7-300 CPUs and SINUMERIK Controller2020-11-10csaf · siemens_psirtDE
A vulnerability in S7-300 might allow an attacker to cause a Denial- of-Service condition on port 102 of the affected devices by sending specially crafted packets. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
- ICSA-20-315-04Siemens SIMATIC S7-300 CPUs and SINUMERIK Controller (Update A)2020-11-10icsa · cisa_csaf_otUS
A vulnerability in S7-300 might allow an attacker to cause a Denial- of-Service condition on port 102 of the affected devices by sending specially crafted packets. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
auch bekannt als (3)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (8)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/pdf/ssa-492828.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2020-15783cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-20-315-04cnnvd
- https://vigilance.fr/vulnerability/SIMATIC-S7-300-denial-of-service-via-Port-102-Packets-33869cnnvd
- https://www.auscert.org.au/bulletins/ESB-2020.4045/cnnvd
- https://www.siemens.com/global/en.htmlPatchcnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-492828.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-492828.pdfMitigationVendor Advisorynvd