CVE-2019-6830

highPriorität · verfolgen · 24EPSS 0.011 · 65. PerzentilEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
1.10% (65th) EPSS
CVSS 7.1 · high
Is it mine?
4 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · bewertet 2026-10-23

A CWE-248: Uncaught Exception vulnerability exists IN Modicon M580 all versions prior to V2.80, which could cause a possible denial of service when sending an appropriately timed HTTP request to the controller.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenModicon M580 Firmware Versions prior to v2.80 installed on Modicon M580 Controllercisa_csaf_ot

    Version sv4.20 of Modicon M580 includes a fix for this vulnerability and is available for download here: STEP 1: Update software and firmware. • On the engineering workstation, update to EcoStruxure Control Expert v16.0: https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-and-firmware • On the Modicon M580 controller, update to firmware SV4.20 or above: https://www.se.com/ww/en/product-range/62098-modicon-m580-epac/#software-and-firmware STEP 2: Update projects in EcoStruxure Control Expert by: • Setting up an application password in the project properties • Changing the version of the controller firmware to match the new firmware version of the target controller STEP 3: Rebuild and transfer projects in EcoStruxure Control Expert: • Rebuild all current projects

    https://www.se.com/ww/en/product-range/62098-modicon-m580-epac/#software-and-firmware
  • MitigationModicon M580 Firmware Versions prior to v2.80 installed on Modicon M580 Controllercisa_csaf_ot

    It is recommended to apply the following mitigations to reduce the risk of exploitation: • Set up an application password in the project properties • Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: https://www.se.com/ww/en/download/document/EIO0000001578/ • Set up a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ NOTE: Use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider using external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 and M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneider-electric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication.

    https://www.se.com/ww/en/download/document/EIO0000001999/
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.1
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.4–7.1

v2.07.1highAV:N/AC:M/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USAusnutzbarkeit 8.6 · Auswirkung 6.9
v3.15.9mediumCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 2.2 · Auswirkung 3.6
v3.15.9mediumCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.15.4mediumCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (4)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-25-114-01Schneider Electric Modicon Controllers (Update A)2019-05-14icsa · cisa_csaf_otUS

    Schneider Electric is aware of multiple vulnerabilities in its Modicon Controller products. The [Modicon Programmable Automation controllers](https://www.se.com/ww/en/product-subcategory/3950-pac-programmable-automation-controllers/) are used for complex networked communication, display and control applications Failure to apply the mitigations or remediations provided below may risk execution of unsolicited command on the PLC which could result in a loss of availability of the controller.

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2019-09-17geändert 2026-06-17
09

Referenzen (5)

Externe Belege — Patches, Meldungen, Analysen.