CVE-2019-18315
highPriorität · verfolgen · 40EPSS 0.025 · 85. PerzentilEUUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 8888/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- BehobenSPPA-T3000 Application Servercisa_csaf_ot
Please contact your Siemens Energy service management organization to obtain the update to Service Pack R8.2 SP2.
- MitigationSPPA-T3000 Application Servercisa_csaf_ot
External components should be connected only to the SPPA-T3000 DMZ; no bridging of an external network to either the Application- or Automation highways is allowed
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 7.5–9.8
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (5)
Betroffene Produkte und Versionsbereiche.
- siemens sppa-t3000 application server< r8.2nvdUScpe:2.3:a:siemens:sppa-t3000_application_server:*:*:*:*:*:*:*:*
- siemens sppa-t3000 application server= r8.2nvdUScpe:2.3:a:siemens:sppa-t3000_application_server:*:*:*:*:*:*:*:*
Advisories (1)
Hersteller- und Ökosystem-Meldungen dazu.
- ICSA-19-351-02Siemens SPPA-T3000 (Update A)2019-12-10icsa · cisa_csaf_otUS
SPPA-T3000 Application Server and MS3000 Migration Server are affected by multiple vulnerabilities. Some of the vulnerabilities can allow an attacker to execute arbitrary code on the server. Exploitation of the vulnerabilities described in this advisory requires access to either Application- or Automation Highway. Both highways should not be exposed if the environment has been set up according to the recommended system configuration in the SPPA-T3000 security manual. In this case Siemens Energy considers the environmental score as CR:L/IR:L/AR:H/MAV:A for vulnerabilities related to the Application Server and CR:L/IR:L/AR:M/MAV:A for vulnerabilities related to the Migration Server. Siemens Energy provides a service pack to fix vulnerabilities on the Application Server and recommends configurations to mitigate the vulnerabilities in the Migration Server. Detailed information will be available for SPPA-T3000 customers in the Siemens Energy Customer Portal (https://cep.siemens-energy.com/).
auch bekannt als (3)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (6)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2019-18315cnnvd
- https://www.auscert.org.au/bulletins/ESB-2019.4705/cnnvd
- https://www.us-cert.gov/ics/advisories/icsa-19-351-02cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdfMitigationVendor Advisorynvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan