CVE-2019-10931

mediumPriorität · verfolgen · 31EPSS 0.015 · 74. PerzentilEURUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.52% (74th) EPSS
CVSS 5 · medium
Is it mine?
45 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-28

A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions ), DIGSI 5 engineering software (All versions < V7.90), SIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.90), SIPROTEC 5 device types 7SS85 and 7KE85 (All versions < V8.01), SIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.59). Specially crafted packets sent to port 443/TCP could cause a Denial of Service condition.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenDIGSI 5 engineering softwarecisa_csaf_ot

    Update to V7.90 or later version and activate the client authorization feature https://support.industry.siemens.com/cs/us/en/view/109767686

  • BehobenSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modulescisa_csaf_ot

    Update to V7.90 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. The latest firmware version for the communication modules can also be found on each device specific download page. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/

  • BehobenSIPROTEC 5 device types 7SS85 and 7KE85cisa_csaf_ot

    Update to V8.01 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/

  • BehobenSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modulescisa_csaf_ot

    Update to V7.59 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. The latest firmware version for the communication modules can also be found on each device specific download page. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/

    https://support.industry.siemens.com/cs/ww/en/
  • MitigationAll other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modulescisa_csaf_ot

    Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)

  • MitigationDIGSI 5 engineering softwarecisa_csaf_ot

    Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)

  • MitigationSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modulescisa_csaf_ot

    Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)

  • MitigationSIPROTEC 5 device types 7SS85 and 7KE85cisa_csaf_ot

    Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)

  • MitigationSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modulescisa_csaf_ot

    Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5–7.5

v2.05mediumAV:N/AC:L/Au:N/C:N/I:N/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 2.9
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (45)

Betroffene Produkte und Versionsbereiche.

20 von 45 angezeigt
05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-19-190-05Siemens SIPROTEC 5 and DIGSI 5 (Update C)2019-07-09icsa · cisa_csaf_otUS

    Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Digital Grid Products can be found at:

06

auch bekannt als (5)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2019-07-11geändert 2026-06-17
08

Referenzen (6)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan