CVE-2019-10919

highPriorität · verfolgen · 39OT-Risiko · erhöhtEPSS 0.027 · 86. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.75% (86th) EPSS
CVSS 7.5 · high
Is it mine?
5 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-28

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenLOGO! 8 BM (incl.'SIPLUS variants)cisa_csaf_ot

    Update to V8.3. Notice that in order to update, a new hardware version is required. https://support.industry.siemens.com/cs/ww/en/view/109783346/

  • MitigationLOGO! 8 BM (incl.'SIPLUS variants)cisa_csaf_ot

    Apply Defense-in-Depth concept, including protection concept outlined in the system manual.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.4
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 7.5–9.4

v2.07.5highAV:N/AC:L/Au:N/C:P/I:P/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 6.4
v3.19.4criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Lprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 5.5
v3.19.4criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L/E:F/RL:O/RC:Csecondary · CISA US
v3.19.4criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Lsecondary · FSTEC (BDU) RU
v3.18.6highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (5)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-19-134-04Siemens LOGO! 8 BM (Update A)2019-05-14icsa · cisa_csaf_otUS

    As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.

06

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2019-05-14geändert 2026-06-17
08

Referenzen (23)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan