CVE-2018-13816

highPriorität · verfolgen · 41OT-Risiko · erhöhtEPSS 0.028 · 86. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.80% (86th) EPSS
CVSS 7.5 · high
Is it mine?
5 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-27

A vulnerability has been identified in TIM 1531 IRC (All version < V2.0). The devices was missing proper authentication on port 102/tcp, although configured. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. At the time of advisory publication no public exploitation of this vulnerability was known.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenTIM 1531 IRC (incl. SIPLUS NET variants)cisa_csaf_ot

    Update to V2.0 https://support.industry.siemens.com/cs/ww/en/view/109762596

  • MitigationTIM 1531 IRC (incl. SIPLUS NET variants)cisa_csaf_ot

    Restrict access to port 102/tcp on TIM 1531 IRC to trusted IP addresses

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

10.0
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 7.5–10

v2.07.5highAV:N/AC:L/Au:N/C:P/I:P/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 6.4
v3.010criticalCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 6
v3.09.1criticalCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.110criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.110criticalAV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (5)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-18-352-05Siemens TIM 1531 IRC Modules2018-12-11icsa · cisa_csaf_otUS

    As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.

06

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2018-12-12geändert 2026-06-17
09

Referenzen (6)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan