CVE-2018-13813

mediumPriorität · verfolgen · 33EPSS 0.017 · 77. PerzentilEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.68% (77th) EPSS
CVSS 5.8 · medium
Is it mine?
33 products
Prüfe deine Angriffsfläche
Who says so?
3 sources
cnnvd · enisa_euvd · cisa_csaf_ot

EPSS · bewertet 2026-10-24

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The webserver of affected HMI devices may allow URL redirections to untrusted websites. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenSIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants)cisa_csaf_ot

    Update SIMATIC WinCC (TIA Portal) to V15 Update 4 or newer, and then update panel to V15 Update 4 or newer. https://support.industry.siemens.com/cs/ww/en/view/109755826

  • BehobenSIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants)cisa_csaf_ot

    Update SIMATIC WinCC (TIA Portal) to V15 Update 4 or newer, and then update panel to V15 Update 4 or newer. https://support.industry.siemens.com/cs/ww/en/view/109755826

  • BehobenSIMATIC HMI KTP Mobile Panels KTP400Fcisa_csaf_ot

    Update SIMATIC WinCC (TIA Portal) to V15 Update 4 or newer, and then update panel to V15 Update 4 or newer. https://support.industry.siemens.com/cs/ww/en/view/109755826

  • BehobenSIMATIC WinCC (TIA Portal)cisa_csaf_ot

    Update to V15 Update 4 or newer https://support.industry.siemens.com/cs/ww/en/view/109755826

  • BehobenSIMATIC WinCC Runtime Advancedcisa_csaf_ot

    Update to V15 Update 4 or newer https://support.industry.siemens.com/cs/ww/en/view/109755826

  • BehobenSIMATIC WinCC Runtime Professionalcisa_csaf_ot

    Update to V15 Update 4 or newer https://support.industry.siemens.com/cs/ww/en/view/109755826

  • MitigationSIMATIC HMI Classic Devices - TP/MP/OP/MP Mobile Panel (incl. SIPLUS variants)cisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants)cisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants)cisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC HMI KTP Mobile Panels KTP400Fcisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC WinCC (TIA Portal)cisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC WinCC Runtime Advancedcisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

  • MitigationSIMATIC WinCC Runtime Professionalcisa_csaf_ot

    Deactivate the web server if not required. The web server is disabled by default.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.1
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.8–8.1

v2.05.8mediumAV:N/AC:M/Au:N/C:P/I:P/A:Nprimary · NVD / NIST USAusnutzbarkeit 8.6 · Auswirkung 4.9
v3.08.1highCVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:Nprimary · NVD / NIST USAusnutzbarkeit 2.8 · Auswirkung 5.2
v3.07.4highCVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N/E:Usecondary · CVSS-BT (t0sche)
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:H/A:N/E:P/RL:O/RC:Csecondary · CISA US
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (33)

Betroffene Produkte und Versionsbereiche.

20 von 33 angezeigt
05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-18-317-08Siemens SIMATIC Panels2018-11-13icsa · cisa_csaf_otUS

    As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2018-12-13geändert 2026-06-17
09

Referenzen (8)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan