CVE-2018-13799

mediumPriorität · verfolgen · 37EPSS 0.023 · 83. PerzentilEURUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
2.25% (83rd) EPSS
CVSS 6.4 · medium
Is it mine?
5 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-27

A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. At the time of advisory publication no public exploitation of this vulnerability was known.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenSIMATIC WinCC OA V3.14 and priorcisa_csaf_ot

    Update to V3.14-P021 and follow the steps at https://portal.etm.at/patchdownload.php?fp=version_3.14/win64vc12/ReadmeP021.txt for adding of modifying WinCC OA users in AD environments. - Download: https://portal.etm.at/index.php?option=com_content&view=category&id=67&layout=blog&Itemid=80

    https://portal.etm.at/patchdownload.php
  • MitigationSIMATIC WinCC OA V3.14 and priorcisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk:allow manual remediation of the vulnerability fixed by WinCC OAV3.14-P021.for maintaining a secured SIMATIC WinCC OA environment. Follow the SIMATIC WinCC OA Security Guideline (available at https://portal.etm.at/index.php?option=com_phocadownload&view=category&id=52:security&Itemid=81)

    https://portal.etm.at/index.php
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.1
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–critical · 6.4–9.1

v2.06.4mediumAV:N/AC:L/Au:N/C:N/I:P/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 4.9
v3.09.1criticalCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 5.2
v3.09.1criticalCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.08.3highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.19.1criticalAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:Hsecondary · FSTEC (BDU) RU
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (5)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-18-254-04ICSA-18-254-04 Siemens SIMATIC WinCC OA2018-09-11icsa · cisa_csaf_otUS

    CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

06

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2018-09-12geändert 2026-06-17
08

Referenzen (7)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan