CVE-2018-11452

highPriorität · verfolgen · 31EPSS 0.024 · 84. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.39% (84th) EPSS
CVSS 7.8 · high
Is it mine?
32 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-28

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the EN100 communication module if oscillographs are running. A manual restart is required to recover the EN100 module functionality. Successful exploitation requires an attacker with network access to send multiple packets to the EN100 module. As a precondition the IEC 61850-MMS communication needs to be activated on the affected EN100 modules. No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenFirmware variant IEC 61850 for EN100 Ethernet modulecisa_csaf_ot

    Update to V4.33 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821 Applying the update causes the module to go through a single restart cycle.

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC104 for EN100 Ethernet modulecisa_csaf_ot

    Update to V1.22 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821 Applying the update causes the module to go through a single restart cycle.

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 61850 for EN100 Ethernet modulecisa_csaf_ot

    Update to V4.33. Applying the update causes the module to go through a single restart cycle. - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet modulecisa_csaf_ot

    See recommendations from section Workaround and Mitigations

  • MitigationFirmware variant IEC 61850 for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Block access to port 102/tcp e.g. with an external firewall.

  • MitigationFirmware variant IEC104 for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Block access to port 102/tcp e.g. with an external firewall.

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet modulecisa_csaf_ot

    See recommendations from section Workaround and Mitigations

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet modulecisa_csaf_ot

    See recommendations from section Workaround and Mitigations

  • MitigationSIPROTEC 5 relays with CPU variants CP200 and the respective Ethernetcisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Block access to port 102/tcp e.g. with an external firewall.

  • MitigationSIPROTEC 5 relays with CPU variants CP300 and CP100 and the respectivecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Block access to port 102/tcp e.g. with an external firewall.

  • MitigationFirmware variant IEC 61850 for EN100 Ethernet modulecisa_csaf_ot

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Block access to port 102/TCP e.g. with an external firewall.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.9–7.8

v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 6.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.05.9mediumCVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.06.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (32)

Betroffene Produkte und Versionsbereiche.

20 von 32 angezeigt
05

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-18-347-02ICSA-18-347-02 Siemens EN100 Ethernet Communication Module and SIPROTEC 5 Relays (Update A)2018-07-11icsa · cisa_csaf_otUS

    CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

  • ICSA-19-038-02ICSA-19-038-02 Siemens EN100 Ethernet Module2019-01-08icsa · cisa_csaf_otUS

    CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

06

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2018-07-23geändert 2026-06-17
09

Referenzen (10)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan