CVE-2017-12069

mediumPriorität · verfolgen · 34EPSS 0.029 · 87. PerzentilDEEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
2.90% (87th) EPSS
CVSS 6.4 · medium
Is it mine?
23 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · bewertet 2026-10-24

An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenSIMATIC IT Production Suitesiemens_psirt

    Update to V7.1 or later version

  • BehobenSIMATIC NET PC Software V14siemens_psirt

    Update to V14 SP1 Update 14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109807351/
  • BehobenSIMATIC WinCC Runtime Professional V14siemens_psirt

    Update to V14 SP1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109746276
  • BehobenSIMATIC IT Production Suitecisa_csaf_ot

    Update to V7.1 or later version

  • BehobenSIMATIC NET PC Software V14cisa_csaf_ot

    Update to V14 SP1 Update 14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109807351/
  • BehobenSIMATIC WinCC Runtime Professional V14cisa_csaf_ot

    Update to V14 SP1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109746276
  • MitigationSIMATIC IT Production Suitesiemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC NET PC Software V14siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC PCS 7siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCCsiemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V13siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V14siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC IT Production Suitecisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC NET PC Software V14cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC PCS 7cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCCcisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V13cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V14cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • Kein Fix geplantSIMATIC PCS 7siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinCCsiemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinCC Runtime Professional V13siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PCS 7cisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinCCcisa_csaf_ot

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinCC Runtime Professional V13cisa_csaf_ot

    Currently no fix is planned

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.2
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.4–8.2

v2.06.4mediumAV:N/AC:L/Au:N/C:P/I:N/A:Pprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 4.9
v3.08.2highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 4.2
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.18.2highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.18.2highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (23)

Betroffene Produkte und Versionsbereiche.

05

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • SSA-535640SSA-535640: Vulnerability in Industrial Products2017-08-30csaf · siemens_psirtDE

    Various industrial products use the Discovery Service of the OPC UA protocol stack by the OPC foundation https://github.com/OPCFoundation/UA-.NETStandard and could therefore be affected by the remote resource consumption attacks (CVE-2017-12069).

  • ICSA-17-243-01Siemens OPC UA Protocol Stack Discovery Service (Update E)2017-08-30icsa · cisa_csaf_otUS

    Various industrial products use the Discovery Service of the OPC UA protocol stack by the OPC foundation https://github.com/OPCFoundation/UA-.NETStandard and could therefore be affected by the remote resource consumption attacks (CVE-2017-12069).

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2017-08-30geändert 2026-06-17
09

Referenzen (10)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan