A vulnerability has been identified in SIMATIC CP 343-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.0.53), SIMATIC CP 443-1 Advanced (incl. SIPLUS NET variant) (All versions < V3.2.17), SIMATIC S7-300 PN/DP CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP CPU family (incl. SIPLUS variants) (All versions). The integrated web server at port 80/TCP or port 443/TCP of the affected devices could allow remote attackers to perform actions with the permissions of an authenticated user, provided the targeted user has an active session and is induced to trigger the malicious request.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.3–8.8

v2.06.8mediumAV:N/AC:M/Au:N/C:P/I:P/A:Pprimary · NVD / NIST USAusnutzbarkeit 8.6 · Auswirkung 6.4
v3.08.8highCVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:Hprimary · NVD / NIST USAusnutzbarkeit 2.8 · Auswirkung 5.9
v3.08.1highCVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.16.3mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (9)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • SSA-603476SSA-603476: Web Vulnerabilities in SIMATIC NET CP 343-1/CP 443-1 Modules and SIMATIC S7-300/S7-400 CPUs2016-11-21csaf · siemens_psirtDE

    SIMATIC CP 343-1 Advanced/CP-443-1 Advanced devices and SIMATIC S7-300/S7-400 CPUs are affected by two vulnerabilities. One of the vulnerabilities could allow remote attackers to perform operations as an authenticated user under certain conditions. Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2016-11-23geändert 2026-06-17
09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan