CVE-2013-2806

highPriorität · verfolgen · 31EPSS 0.039 · 90. PerzentilEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
3.85% (90th) EPSS
CVSS 7.8 · high
Is it mine?
26 products
Prüfe deine Angriffsfläche
Who says so?
4 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · bewertet 2026-10-27

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “End of Current Record” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size.” Then the service will calculate an incorrect value for the “End of Current Record” field causing access violations that lead to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation security advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Noch kein Hersteller-Fix; eine Mitigation ist verfügbar.

  • MitigationFactoryTalk Services Platform and RSLinx Enterprisecisa_csaf_ot

    Rockwell Automation’s recommendation to asset owners using FTSP or RSLinx CPR9 through CPR9-SR4 is to upgrade to CPR9-SR5 or newer. Rockwell Automation also recommends that all asset owners using FTSP or RSLinx CPR9-SR5 and newer should apply the correlating patch for the version they are using.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.9–7.8

v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USAusnutzbarkeit 10 · Auswirkung 6.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 3.6
v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Csecondary · CISA US
v3.06.9mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (26)

Betroffene Produkte und Versionsbereiche.

20 von 26 angezeigt
05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-13-095-02ARockwell Automation FactoryTalk and RSLinx Vulnerabilities2013-01-07icsa · cisa_csaf_otUS

    This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

06

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2019-03-26geändert 2026-06-16
09

Referenzen (5)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan