VDE-2021-050

csafDEwago_psirt

WAGO: Multiple devices affected by Vulnerabilities in NUCLEUS TCP Stack.

Advisory ansehen veröffentlicht 2021-11-16

Multiple vulnerabilities were reported in the Nucleus Real-Time Operating System (RTOS). The Nucleus RTOS is an essential component in several WAGO PLCs and fieldbus coupler. WAGO uses older Versions of the Nucleus RTOS also in legacy products. For additional information please consult the official Siemens advisory: • Advisory SSA-044112

01

beschreibt (12)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2021-31890UScritical9.1—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versi…
CVE-2021-31889UScritical9.1—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versi…
CVE-2021-31888UShigh8.8—
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC…
CVE-2021-31887UShigh8.8—
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC…
CVE-2021-31886UScritical9.8—
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC…
CVE-2021-31884UScritical9.8—
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC…
CVE-2021-31883UShigh7.5—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP ACK mes…
CVE-2021-31882UShigh7.5—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application do…
CVE-2021-31881UShigh7.5—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). When processing a DHCP OFFER m…
CVE-2021-31346UScritical9.1—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versi…
CVE-2021-31345UScritical9.1—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versi…
CVE-2021-31344USmedium5.3—
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versi…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (24)

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Mitigation

    1. Use general security best practices to protect systems from local and network attacks. 2. Do not allow direct access to the device from untrusted networks. 3. Update to the latest firmware according to the table in chapter solutions. 4. Disable the DHCP, DNS and the FTP port 21. 5. Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy. The BSI provides general information on securing ICS in the ICS Compendium [BSI2013] and on the official BSI website [BSI2021]. For fieldbus coupler: - 750-331 - 750-352/xxx-xxx For PLCs: - 750-829 - 750-831/xxx-xxx - 750-852 - 750-880/xxx-xxx - 750-881 - 750-889 The listed fieldbus coupler and PLCs above are based on Nucleus V1 RTOS. At the moment there are no updates for this version available. Due to this reason WAGO recommends according to the recommendations of the BSI to implement the following measures: 1. Enforce segmentation controls and proper network hygiene to reduce the risk of vulnerable devices. Restrict external communication paths and isolate vulnerable devices in zones as a mitigating measure. 2. Ensure DHCP responses from non-authorized servers are blocked or discarded. 3. Monitor network traffic for anomalies and discard invalid packets. 4. Disable or block FTP, DHCP, DNS especially on critical network segments 5. Please check regularly https://certvde.com/de/ for an update of this Advisory.

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |

  • Behoben

    For fieldbus coupler: - 750-332 - 750-362/xxx-xxx - 750-363/xxx-xxx - 750-364/xxx-xxx - 750-365/xxx-xxx For PLCs: - 750-823 - 750-832/xxx-xxx - 750-862 - 750-890/xxx-xxx - 750-891 - 750-893 We recommend all effected users to update to the firmware version listed below: | Article Number | Fixed in Firmware Version | Availability | |----------------------|----------------------------|---------------------------| | 750-823 | >=FW10 | January 2022 | | 750-832/000-00x | >=FW10 | After BACnet certification| | 750-862 | >=FW10 | January 2022 | | 750-890/xxx-xxx | >=FW10 | January 2022 | | 750-891 | >=FW10 | January 2022 | | 750-893 | >=FW10 | January 2022 | | 750-332 | >=FW10 | After BACnet certification| | 750-362/xxx-xxx | >=FW10 | January 2022 | | 750-363/xxx-xxx | >=FW10 | January 2022 | | 750-364/xxx-xxx | >=FW10 | January 2022 | | 750-365/xxx-xxx | >=FW10 | January 2022 |