SSA-111512

csafDEsiemens_psirt

SSA-111512: Client-side Authentication in SIMATIC WinCC OA

Advisory ansehen veröffentlicht 2022-06-21

SIMATIC WinCC OA implements client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated. Siemens recommends to enable server-side authentication (SSA) or Kerberos authentication for all WinCC OA projects, as documented in the WinCC OA Security Guideline. In SIMATIC WinCC OA server-side authentication is available since V3.15 (and offered as the default configuration since V3.17). Additional information can be found at: https://cert-portal.siemens.com/productcert/news.html?id=21.

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2022-33139UScritical9.8—
A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All versions), SIMATIC WinCC OA V3.16 (All versions in default conf…