Rockwell Automation FactoryTalk Historian Site Edition
Successful exploitation of these vulnerabilities could allow an attacker to obtain a valid authentication token, perform a denial of service, or crash the system.
beschreibt (3)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2025-13036US | — | — | ||
An authentication
bypass security issue exists within FactoryTalk Historian Site Edition. By
continually sending requests to the login endpoint, an attacker may obtain a
valid auth… | ||||
| CVE-2025-44019US | — | — | ||
AVEVA PI Data Archive products are vulnerable to an uncaught exception that, if
exploited, could allow an authenticated user to shut down certain
necessary PI Data Archive subsys… | ||||
| CVE-2025-36539US | — | — | ||
AVEVA PI Data Archive products
are vulnerable to an uncaught exception that, if exploited, could allow
an authenticated user to shut down certain necessary PI Data Archive
subsy… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
- ICS Advisory ICSA-26-169-03 JSONself
- ICSA Advisory ICSA-26-169-03 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
Behebungen (3)
- MitigationFactoryTalk Historian SE
For more information, see Rockwell Automation Security Advisory SD1773 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html)
https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html - MitigationFactoryTalk Historian SE
Mitigations and Workarounds for CVE-2025-36539 & CVE-2025-44109: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and also consider the following: Monitor liveness of PI Network Manager and PI Archive Subsystem services. Set the PI Network Manager and PI Archive Subsystem services to automatically restart. Limit port 5450 access to trusted workstations and software. For a list of PI System firewall port requirements, see knowledge base article KB01162 - Firewall Port Requirements. For a starting point on PI system security best practices, see knowledge base article KB00833 - Best practices for securing your PI Server.
- MitigationFactoryTalk Historian SE
Rockwell Automation recommends the following: Mitigations and Workarounds for CVE-2025-13036: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and consider applying the available patch (BF32850) for their current version (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US).
https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US