ICSA-26-169-03

icsaUScisa_csaf_ot

Rockwell Automation FactoryTalk Historian Site Edition

Advisory ansehen veröffentlicht 2026-06-18

Successful exploitation of these vulnerabilities could allow an attacker to obtain a valid authentication token, perform a denial of service, or crash the system.

01

beschreibt (3)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2025-13036US——
An authentication bypass security issue exists within FactoryTalk Historian Site Edition. By continually sending requests to the login endpoint, an attacker may obtain a valid auth…
CVE-2025-44019US——
AVEVA PI Data Archive products are vulnerable to an uncaught exception that, if exploited, could allow an authenticated user to shut down certain necessary PI Data Archive subsys…
CVE-2025-36539US——
AVEVA PI Data Archive products are vulnerable to an uncaught exception that, if exploited, could allow an authenticated user to shut down certain necessary PI Data Archive subsy…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (3)

  • MitigationFactoryTalk Historian SE

    For more information, see Rockwell Automation Security Advisory SD1773 (https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html)

    https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1773.html
  • MitigationFactoryTalk Historian SE

    Mitigations and Workarounds for CVE-2025-36539 & CVE-2025-44109: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and also consider the following: Monitor liveness of PI Network Manager and PI Archive Subsystem services. Set the PI Network Manager and PI Archive Subsystem services to automatically restart. Limit port 5450 access to trusted workstations and software. For a list of PI System firewall port requirements, see knowledge base article KB01162 - Firewall Port Requirements. For a starting point on PI system security best practices, see knowledge base article KB00833 - Best practices for securing your PI Server.

  • MitigationFactoryTalk Historian SE

    Rockwell Automation recommends the following: Mitigations and Workarounds for CVE-2025-13036: Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices and consider applying the available patch (BF32850) for their current version (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US).

    https://support.rockwellautomation.com/app/answers/answer_view/a_id/1157978/loc/en_US
scry

Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan