ICSA-23-157-02

icsaUScisa_csaf_ot

Mitsubishi Electric MELSEC iQ-R Series/iQ-F Series (Update C)

Advisory ansehen veröffentlicht 2023-06-06

Successful exploitation of these vulnerabilities could allow a remote unauthenticated attacker to connect to the module via FTP and bypass authentication to log in.

01

beschreibt (4)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2023-2063UShigh7.3—
Unrestricted Upload of File with Dangerous Type vulnerability in FTP function on Mitsubishi Electric Corporation MELSEC iQ-R Series EtherNet/IP module RJ71EIP91 and MELSEC iQ-F Ser…
CVE-2023-2062USmedium6.2—
Missing Password Field Masking vulnerability in Mitsubishi Electric Corporation EtherNet/IP configuration tools SW1DNN-EIPCT-BD and SW1DNN-EIPCTFX5-BD allows a remote unauthenticat…
CVE-2023-2061UShigh7.5OT erhöht—
Use of Hard-coded Password vulnerability in FTP function on Mitsubishi Electric Corporation MELSEC iQ-R Series EtherNet/IP module RJ71EIP91 and MELSEC iQ-F Series EtherNet/IP modul…
CVE-2023-2060UShigh7.5—
Weak Password Requirements vulnerability in FTP function on Mitsubishi Electric Corporation MELSEC iQ-R Series EtherNet/IP module RJ71EIP91 and MELSEC iQ-F Series EtherNet/IP modul…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (16)

  • MitigationFX5-ENET/IP

    Allow only trusted users to log in or remotely log in.

  • MitigationFX5-ENET/IP

    Allow only trusted users to log in or remotely log in.

  • MitigationFX5-ENET/IP

    Allow only trusted users to log in or remotely log in.

  • MitigationRJ71EIP91

    Allow only trusted users to log in or remotely log in.

  • MitigationRJ71EIP91

    Allow only trusted users to log in or remotely log in.

  • MitigationRJ71EIP91

    Allow only trusted users to log in or remotely log in.

  • MitigationSW1DNN-EIPCT-BD

    Allow only trusted users to log in or remotely log in.

  • MitigationSW1DNN-EIPCTFX5-BD

    Allow only trusted users to log in or remotely log in.

  • BehobenFX5-ENET/IP

    FX5-ENET/IP firmware version "1.106" or later: The FTP function can be disabled. To prevent unauthorized access from outside, set the connection to "Deny connection" in the EtherNet/IP Configuration Tool for FX5-ENET/IP Tool connection setting change function and disable the module's FTP function, except when configuring with the EtherNet/IP Configuration Tool for FX5-ENET/IP. For detailed configuration instructions, refer to the following manuals: "Tool connection setting change function" in the "Details of buffer memory addresses" in the "Appendix 4 Buffer Memory" in the "MELSEC iQ-F FX5 EtherNet/IP Module User's Manual."

  • BehobenFX5-ENET/IP

    FX5-ENET/IP firmware version "1.106" or later: The FTP function can be disabled. To prevent unauthorized access from outside, set the connection to "Deny connection" in the EtherNet/IP Configuration Tool for FX5-ENET/IP Tool connection setting change function and disable the module's FTP function, except when configuring with the EtherNet/IP Configuration Tool for FX5-ENET/IP. For detailed configuration instructions, refer to the following manuals: "Tool connection setting change function" in the "Details of buffer memory addresses" in the "Appendix 4 Buffer Memory" in the "MELSEC iQ-F FX5 EtherNet/IP Module User's Manual."

  • BehobenFX5-ENET/IP

    FX5-ENET/IP firmware version "1.106" or later: The FTP function can be disabled. To prevent unauthorized access from outside, set the connection to "Deny connection" in the EtherNet/IP Configuration Tool for FX5-ENET/IP Tool connection setting change function and disable the module's FTP function, except when configuring with the EtherNet/IP Configuration Tool for FX5-ENET/IP. For detailed configuration instructions, refer to the following manuals: "Tool connection setting change function" in the "Details of buffer memory addresses" in the "Appendix 4 Buffer Memory" in the "MELSEC iQ-F FX5 EtherNet/IP Module User's Manual."

  • BehobenRJ71EIP91

    Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of exploiting these vulnerabilities common to RJ71EIP91 and FX5-ENET/IP:

  • BehobenRJ71EIP91

    Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of exploiting these vulnerabilities common to RJ71EIP91 and FX5-ENET/IP:

  • BehobenRJ71EIP91

    Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of exploiting these vulnerabilities common to RJ71EIP91 and FX5-ENET/IP:

  • BehobenSW1DNN-EIPCT-BD

    Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of exploitation of these vulnerabilities common to SW1DNN-EIPCT-BD and SW1DNN-EIPCTFX5-BD:

  • BehobenSW1DNN-EIPCTFX5-BD

    Mitsubishi Electric recommends that customers take the following mitigation measures to minimize the risk of exploitation of these vulnerabilities common to SW1DNN-EIPCT-BD and SW1DNN-EIPCTFX5-BD: