Schneider Electric Galaxy VS, Galaxy VL, Galaxy VXL (Update A)
Schneider Electric is aware of a vulnerability disclosed on the Erlang/OTP's SSH Server component used Schneider Electric Galaxy VS, VL, and VXL.Many vendors, including Schneider Electric, embed the Erlang/OTP's SSH Server in their offers.The Galaxy VS, Galaxy VL, Galaxy VXL products are 3-phase UPS for data centers and other business critical applications.Failure to apply the mitigation provided below may risk unauthenticated remote code execution (RCE), which could impact the monitoring capabilities of the UPS and potential UPS operation.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2025-32433US | —OT kritisch | KEV | ||
Erlang/OTP is a set of libraries for the Erlang programming language. Prior to versions OTP-27.3.3, OTP-26.2.5.11, and OTP-25.3.2.20, a SSH server may allow an attacker to perform… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
- Galaxy VS, Galaxy VL, Galaxy VXL - SEVD-2025-133-05 PDF Versionself
- Galaxy VS, Galaxy VL, Galaxy VXL - SEVD-2025-133-05 CSAF Versionself
- GitHub Security Advisoryexternal
- ICS Advisory ICSA-25-140-07 JSONself
- ICS Advisory ICSA-25-140-07 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
Behebungen (6)
- MitigationGalaxy VL
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: 1. Log on to the NMC4 via the Web Interface. Once logged into the system, navigate to the Console settings page from the menu bar by selecting Configuration -> Network -> Console -> Access 2. From the Console setting screen, uncheck the enable SSH/SFTP/SCP check box -> Click Apply As an alternative, setup network segmentation and implement a firewall to block all unauthorized access to SSH port 22/TCP. If assistance is needed applying the above mitigation, please contact our technical support team: https://www.se.com/ww/en/work/support/ To learn more, we recommend reviewing the Network Management Card 4 Security Handbook for specific actions available here to secure your devices further: https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric's security notification service here: https://www.se.com/en/work/support/cybersecurity/security-notifications.jsp
https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ - MitigationGalaxy VS
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: 1. Log on to the NMC4 via the Web Interface. Once logged into the system, navigate to the Console settings page from the menu bar by selecting Configuration -> Network -> Console -> Access 2. From the Console setting screen, uncheck the enable SSH/SFTP/SCP check box -> Click Apply As an alternative, setup network segmentation and implement a firewall to block all unauthorized access to SSH port 22/TCP. If assistance is needed applying the above mitigation, please contact our technical support team: https://www.se.com/ww/en/work/support/ To learn more, we recommend reviewing the Network Management Card 4 Security Handbook for specific actions available here to secure your devices further: https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric's security notification service here: https://www.se.com/en/work/support/cybersecurity/security-notifications.jsp
https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ - MitigationGalaxy VXL
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: 1. Log on to the NMC4 via the Web Interface. Once logged into the system, navigate to the Console settings page from the menu bar by selecting Configuration -> Network -> Console -> Access 2. From the Console setting screen, uncheck the enable SSH/SFTP/SCP check box -> Click Apply As an alternative, setup network segmentation and implement a firewall to block all unauthorized access to SSH port 22/TCP. If assistance is needed applying the above mitigation, please contact our technical support team: https://www.se.com/ww/en/work/support/ To learn more, we recommend reviewing the Network Management Card 4 Security Handbook for specific actions available here to secure your devices further: https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric's security notification service here: https://www.se.com/en/work/support/cybersecurity/security-notifications.jsp
https://www.se.com/us/en/download/document/SPD_CCON-B8EJSJ_EN/ - BehobenGalaxy VL
Version 18.10.0 of Galaxy VL includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.
- BehobenGalaxy VS
Version 6.123.0 of Galaxy VS includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.
- BehobenGalaxy VXL
Version 15.29.0 of Galaxy VXL includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.
Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan