ICSA-25-093-01

icsaUScisa_csaf_ot

Hitachi Energy RTU500 Series (Update B)

Advisory ansehen veröffentlicht 2025-03-25

Hitachi Energy is aware of the vulnerabilities, CVE-2024-10037, CVE-2024-11499, CVE-2024-12169, and CVE-2025-1445 in the RTU500 Web server component, the IEC 60870-5-104 controlled station implementation and IEC 61850 implementation, that affects the RTU500 versions that are listed below. An attacker successfully exploiting these vulnerabilities could trigger a restart of a RTU500 CMU. Please refer to the Recom-mended Immediate Actions for information about the available mitigation/remediation strategies.

01

beschreibt (4)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2025-1445US——
A vulnerability exists in RTU IEC 61850 client and server functionality that could impact the availability if renegotiation of an open IEC61850 TLS connection takes place in specif…
CVE-2024-12169US——
A vulnerability exists in RTU500 IEC 60870-5-104 controlled station functionality and IEC 61850 functionality, that allows an attacker performing a specific attack sequence to rest…
CVE-2024-11499US——
A vulnerability exists in RTU500 IEC 60870-4-104 controlled station functionality, that allows an authenticated and authorized attacker to perform a CMU restart. The vulnerability…
CVE-2024-10037US——
A vulnerability exists in the RTU500 web server component that can cause a denial of service to the RTU500 CMU application if a specially crafted message sequence is executed on a…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (15)

  • MitigationCMU Firmware

    For all versions, apply General Mitigation Factors/Workarounds. Upgrade the system once remediated version in available, or apply general mitigation factors.

  • MitigationCMU Firmware

    For all versions, apply General Mitigation Factors/Workarounds. Upgrade the system once remediated version in available, or apply general mitigation factors.

  • MitigationCMU Firmware

    For all versions, apply General Mitigation Factors/Workarounds. Upgrade the system once remediated version in available, or apply general mitigation factors.

  • MitigationCMU Firmware

    For all versions, apply General Mitigation Factors/Workarounds. Upgrade the system once remediated version in available, or apply general mitigation factors.

  • MitigationCMU Firmware

    For all versions, apply General Mitigation Factors/Workarounds. Upgrade the system once remediated version in available, or apply general mitigation factors.

  • BehobenCMU Firmware

    Fixed in version 13.7.1. Update to CMU Firmware version 13.7.7

  • BehobenCMU Firmware

    Update to CMU Firmware version 13.5.4

  • BehobenCMU Firmware

    Update to CMU Firmware version 13.7.7

  • BehobenCMU Firmware

    Update to CMU Firmware version 13.7.7

  • BehobenHitachi Energy RTU500 series CMU Firmware version 12.0.1 – 12.0.14

    Update to CMU Firmware version 12.7.8 when available

  • BehobenHitachi Energy RTU500 series CMU Firmware version 12.2.1 – 12.2.12

    Update to CMU Firmware version 12.7.8 when available

  • BehobenHitachi Energy RTU500 series CMU Firmware version 12.4.1 – 12.4.11

    Update to CMU Firmware version 12.7.8 when available

  • BehobenHitachi Energy RTU500 series CMU Firmware version 12.6.1 – 12.6.10

    Update to CMU Firmware version 12.7.8 when available

  • BehobenHitachi Energy RTU500 series CMU Firmware version 12.7.1 – 12.7.7

    Update to CMU Firmware version 12.7.8 when available

  • BehobenHitachi Energy RTU500 series CMU Firmware version 13.2.1 – 13.2.7

    Fixed in version 13.7.1. Update to CMU Firmware version 13.7.7