Hitachi Energy Relion 670/650/SAM600-IO
Hitachi Energy is aware of a report from U.S. Department of Energy CyTRICS researcher of a vulnerability in the Relion 670/650/SAM600-IO series versions listed below. Recommended action for each affected version is listed in the Recommended Immediate Actions Section. An attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2021-35535US | high8.1OT erhöht | — | ||
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reb… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
- Cybersecurity Advisory - Insecure Boot Image Vulnerability in Hitachi Energy Relion 670/650/SAM600-IO series Productsself
- ICS Advisory ICSA-21-336-05 JSONself
- Recommended Practicesexternal
- ICS Advisory ICSA-21-336-05 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
Behebungen (5)
- MitigationRelion 650
Apply General Mitigation Factors
- MitigationRelion 670
Apply General Mitigation Factors
- BehobenRelion 650
Update to 2.2.1.7 version or latest
- BehobenRelion 670
Update to 2.2.1.7 version or latest
- BehobenSAM-IO
Update to 2.2.1.7 version or latest
Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.